Question 8.4: The effect of motors is neglected in Example 8.3. Calculate ......

The effect of motors is neglected in Example 8.3. Calculate the partial currents from the motors at 13.8 kV. Do these motor contributions need to be considered in IEC calculations for a fault at F2? Also, calculate the peak current and the asymmetrical breaking current for a fault at F3 on the 4.16 kV bus.

Step-by-Step
The 'Blue Check Mark' means that this solution was answered by an expert.
Learn more on how do we answer questions.

Effect of Motor Contribution at 13.8 kV Bus, Fault F2
For a fault at the 13.8 kV bus F2, an equivalent impedance of the motors through transformers and cables is calculated. The partial currents from medium- and low-voltage motors are calculated in Tables 8.10 and 8.11, respectively. The equivalent impedance of low-voltage motors of two identical groups, from Table 8.11, is 6.45 + j15.235 per unit.
The per unit impedance of transformer T3 from Table 7.13 is 0.639 + j3.780. Therefore, the lowvoltage motor impedance through transformer T3, seen from the 4.16 kV bus, is 7.089 + j19.015 per unit.
From Table 8.10, the equivalent impedance of medium-voltage motors is 0.58 + j4.55 pu. The equivalent impedances of low- and medium-voltage motors in parallel are
(7.089 + j19.015) || (0.58 + j4.55) = 0.637 + j3.707
To this, add the impedance of cable C1 and transformer T2 from Table 7.13, which gives 0.701 + j4.606 pu. This is the equivalent impedance as seen from the 13.8 kV bus. Thus, the initial short-circuit current from the motor contribution is 1.1/(0.701 + j4.606) per unit = |0.99| kA.
The effect of motors in this example can be ignored, and the above calculation of currents from motor contributions is not necessary. From Equation 8.33,
\frac{ΣP_{rM}}{ΣS_{rT}}≤ \frac{0.8}{|\frac{c100 ΣS_{r\overline{T}}}{S^{\prime \prime}_{kQ} – \ 0.3}|}      (8.33)
ΣP_{rm} = sum of the active powers of all medium- and low-voltage motors = 0.86 MW. Also, ΣS_{rT} = rated apparent power of the transformer = 7.5 MVA. The left-hand side of Equation 8.33 = 0.1147. Symmetrical short-circuit power at the point of connection, without effect of motors, is
S^{\prime \prime}_{kQ} = \sqrt{3} I^{\prime \prime}_{k}U_{n} = \sqrt{3} (56.5)(13.8) = 1350.7 \ MVA
The right-hand side of Equation 8.33 gives 2.571, and the identity in Equation 8.33 is satisfied. The effect of motors can be ignored for a fault at 13.8 kV.
If the calculation reveals that motor contributions should be considered, we have to modify i_{p} at the fault point. This requires calculation of χ, which is not straightforward. High-voltage motors have χ = 1.75 or 1.65, and low-voltage motors have χ = 1.65. For a combination load, χ = 1.7 can be used to calculate i_{p} approximately.
Three-phase short-circuit at F3. For a fault at F3, we will first calculate the motor contributions. The low-voltage motor impedance plus transformer T3 impedance is 7.089 + j19.015, as calculated above. The initial short-circuit contribution from the low-voltage motor contribution is 1.1/(7.089 + j19.015) = 0.019 – j0.051 pu or | I^{\prime \prime}_{k}| = 0.76 kA. Medium-voltage impedance, from Table 8.10, is 0.58 + j4.55 per unit. The medium-voltage motor contribution is 0.028- j0.239 pu or | I^{\prime \prime}_{k}| = 3.43 kA.
To calculate the generator and utility source contributions, the impedances Z_{G,PSU} are in || with (Z_{T,PSU} + Z_{Q}), i.e., 0.0074 + j0.1483 in || with 0.006074 + j0.16378. This gives 0.0034 + j0.0778 pu. Add transformer T2 impedance (0.06349 + j0.89776) and cable C1 impedance (0.00038 + j0.00101) from Table 7.13. This gives an equivalent impedance of 0.0673 + j0.976 per unit. Thus, the initial short-circuit current is 0.077 – j1.122 per unit or | I^{\prime \prime}_{k}| = 15.61 kA. The total initial symmetrical
current, considering low- and medium-voltage motor contributions, is 19.80 kA. To calculate i_{p}, χ must be calculated for the component currents.
For contribution through transformer T2, using Equation 8.4:
χ= 1.02 + 0.98e^{-3R/X}        (8.4)
χ_{AT} = 1.02 + 0.98ε^{-3(0.06895)}
= 1.82
As this is calculated from a meshed network, a safety factor of 1.15 is applicable, i.e., χ = 1.15 multiplied by 1.82 = 2.093. However, for high-voltage systems, χ is not > 2.0. This gives i_{pAT} = (2)( \sqrt{2} )(15.65) = 44.27. For medium-voltage motors, χ can be calculated from Table 8.10:
χ_{MV} =\frac{ i_{p}}{ \sqrt{2}  I^{\prime \prime}_{k}}= \frac{7.39}{ \sqrt{2}(3.06)} = 1.71
For low-voltage motors through transformer T3:
χ_{LVT} = 1.02 + 0.98e^{-3(6.97/19.02)} = 1.346
i_{pLV} = (1.346)( \sqrt{2} )(0.76) = 1.45 \ kA
Total peak current by summation = (44.27 +7.39 + 1.45) = 53.11 kA.
The breaking current is the summation of individual breaking currents:
Breaking current through transformers at 4.16 kV = | I^{\prime \prime}_{k}| = 15.65 kA
Breaking current medium-voltage motors from Table 8.10 = 1.78 kA
For low-voltage motors with I^{\prime \prime}_{KM}/I_{RM} = 6.6, μ = 0.78, q can be conservatively calculated for m ≤ 0.3 and p = 2. This gives q = 0.64. The component breaking current from low-voltage motors is therefore, 0.78 × 0.64 × 0.76 = 0.38 kA. Total symmetrical breaking current = 17.81 kA.
To calculate the asymmetrical breaking current, the dc components of the currents should be calculated:
The dc component of the low-voltage motor contribution is practically zero.
The dc component of the medium-voltage motors at contact parting time of 0.05 s = 0.5 kA.
The dc component of current through transformer T2 = 6.07 kA.
Total dc current at contact parting time = 6.57 kA; this gives asymmetrical breaking current of 18.98 kA.
The results are shown in Table 8.8.

TABLE 8.10
Partial Short-Circuit Currents from Asynchronous Medium-Voltage Motors: Example 8.4
Parameter 2425 hp 300 hp 500 hp Sum (Σ)
Power output, P_{rm} (MW) 1.81 0.224 0.373
Quantity 1 3 2
Power factor (cos \phi) 0.93 0.92 0.92
Efficiency (η_{r}) 0.96 0.93 0.94
Ratio, locked rotor current to
full load current (I_{LR}/I_{rM})
6 6 6
Pair of poles (p) 1 1 2
Sum of MVA (S_{rM}) 2.03 0.78 0.86
Sum, rated current (I_{rM}) 0.28 0.11 0.12
I^{\prime \prime}_{K}/I_{rM} 6.6 6.6 6.6
Power per pole pair (m) 1.81 0.223 0.186
R_{M}/X_{M} 0.10 0.15 0.15
κ_{m} 1.75 1.65 1.65
μ 0.78 0.78 0.78
q 0.86 0.61 0.59
I^{\prime \prime}_{KM} 1.68 0.66 0.72 Σ = 3.06
i_{pM} 4.18 1.54 0.67 Σ = 7.39
i_{bm} 1.13 0.32 0.33 Σ = 1.78
Z_{M} (pu) 8.23 21.41 1.42
X_{M} (pu) 0.995 Z_{M} = 8.189 0.989 Z_{M} = 21.17 0.989 Z_{M} = 19.21
R_{M} (pu) 0.1 X_{M} = 0.82 0.15 X_{M} = 3.18 0.15 X_{M} = 2.88
Cable C2 0.068 + j0.104
Σ MV motors and cable 0.58 + j4.55
TABLE 8.11
Low-Voltage Motors, Partial Short-Circuit Current Contributions: Example 8.4
Parameter Motors M4, M5, and M6 (or Identical Group of Motors M40 , M50 , and M6) Remarks
P_{rm} (MW) 0.43 Calculated active power rating
of the motor group
Sum of MVA (S_{rM}) 0.52 Active power rating divided
by power factor
R_{M}/X_{M} 0.42 From Equation 8.20

\frac{R_{M}}{X_{M}} = 0.10 with X_{M} = 0.995 Z_{M} for high-voltage motors with powers [/latex]P_{rM}[/latex] per pair of poles  1 ≥ MW
\frac{R_{M}}{X_{M}} = 0.15 with X_{M} = 0.989 Z_{M} for high-voltage motors with powers PrM per pair of poles <1 MW
\frac{R_{M}}{X_{M}} = 0.42 with X_{M} = 0.922 Z_{M} for low-voltage motor groups with connection cables           (8.20)

for group of motors connected through cables

χ_{m} 1.3 From Equation 8.4
x = 1.02 + 0.98e^{-3R/X}        (8.4)
Ratio, locked rotor current to full load current (I_{LR}/I_{rM}) 6
Z_{M} in per unit 100 MVA base 32.12
X_{M} in per unit 100 MVA base 0.922 Z_{M} = 29.61 Equation 8.20
R_{M} in per unit 100 MVA base 0.42 X_{M} = 12.44 Equation 8.20
Cables C3 or C4 in per unit 100 MVA base 0.46 + j0.860 Table 7.13
TABLE 7.13
Impedance Data (Example 7.2)
Description of Equipment Per Unit Resistance on a 100 MVA Base Per Unit Reactance on a 100 MVA Base
Utility’s 138 kV source, three-phase fault level = 4556 MVA, X/R ratio = 13.4 0.00163 0.02195
112.1 MVA generator, saturated sub transient = 16.4% data in Table 6.1 0.001133 0.14630
Transformer T_{1}, 60/100 MVA, Z = 7.74%, X/R = 32 0.00404 0.12894
Transformer T_{3}, 1.5 MVA, Z = 5.75%, X/R = 5.9% 0.06349 0.89776
Transformer T_{2}, 7.5 MVA, Z = 6.75%, X/R = 14.1 0.63909 3.77968
3.8 kV cable C_{1}, 2-1/C per phase, 1000 KCMIL, in steel conduit, 80 ft 0.00038 0.00101
4.16 kV cable C_{2}, 1-1/C per phase, 500 KCMIL, in steel conduit, 400 ft 0.06800 0.10393
0.48 kV cables C_{3} and C_{4}, 3-1/C per phase, 750 KCMIL, in steel conduit, 150 ft 0.46132 0.85993
M_{1}, 2425 hp, 2-pole induction motor 0.23485 7.6517
M_{2}, 300 hp, 2-pole induction motors, 3 each 1.2997 19.532
M_{3}, 500 hp, 2-pole induction motors, 2 each 0.90995 17.578
M_{4} and M^{\prime}_{4}, 150 hp, 4-pole induction motor 11.714 117.19
M_{5} and M^{\prime}_{5}, 75 hp, 4-pole, induction motor, 3 each 10.362 74.222
M_{6} and M^{\prime}_{6}, 200 hp induction motors, lumped, < 50 hp 20.355 83.458
B_{1}, 5 kA bus duct, phase-segregated, 40 ft 0.0005 0.00004
B_{2}, 5 kA bus duct, phase-segregated, 80 ft 0.00011 0.00008
TABLE 8.8
Examples 8.3 and 8.4: Comparative Results of Three-Phase Short-Circuit Calculations
Fault Location Calculation Method First-Cycle Current kA asym. Peak (ANSI) or Peak Current i_{p} (IEC) Interrupting Duty Current (ANSI) or I_{basym}(IEC)
Fl (138 kV) ANSI calculation
IEC calculation
53.1
57.53
20.54 × 1.2 = 24.65 (Example 7.2)
26.47
F2(13.8 kV) ANSI calculation
IEC calculation
155.69
147.61
71.69 × 1.1 = 78.86 (Example 7.3)
74.21
F3 (4.16 kV) ANSI calculation
IEC calculation
46.23
53.11
16.35 × 1.1 = 17.99 (Note)
18.98

Note: Not calculated in chapter 7, a reader can verify the calculations shown.

TABLE 6.1
Generator Data
Description Symbol Data
Generator
112.1 MVA, 2-pole, 13.8 kV, 0.85 PF, 95.285 MW,
4690 A, 0.56 SCR, 235 field V, wye connected
Per unit reactance data, direct axis
Saturated synchronous X_{dv} 1.949
Unsaturated synchronous X_d 1.949
Saturated transient X^\prime_{dv} 0.207
Unsaturated transient X^\prime_d 0.278
Saturated subtransient X^{\prime\prime}_{dv} 0.164
Unsaturated subtransient X^{\prime\prime}_{d} 0.193
Saturated negative sequence X_{2\text{v}} 0.137
Unsaturated negative sequence X_{2I} 0.185
Saturated zero sequence X_{0\text{v}} 0.092
Leakage reactance, overexcited X_{0I} 0.111
Leakage reactance, underexcited X_{LM,OXE} 0.164
X_{LM,UXE} 0.164
Per unit reactance data, quadrature axis
Saturated synchronous X_{q\text{v}} 1.858
Unsaturated synchronous X_q 1.858
Unsaturated transient X^\prime_q 0.434
Saturated subtransient X^{\prime\prime}_{q\text{v}} 0.140
Unsaturated subtransient X^{\prime\prime}_{q} 0.192
Field time constant data, direct axis
Open circuit T^\prime_{d0} 5.615
Three-phase short-circuit transient T^\prime_{d3} 0.597
Line-to-line short-circuit transient T^\prime_{d2} 0.927
Line-to-neutral short-circuit transient T^\prime_{d1} 1.124
Short-circuit subtransient T^{\prime\prime}_{d} 0.015
Open circuit subtransient T^{\prime\prime}_{d0} 0.022
Field time constant data quadrature axis
Open circuit T^\prime_{q0} 0.451
Three-phase short-circuit transient T^\prime_{q} 0.451
Short-circuit subtransient T^{\prime\prime}_{q} 0.015
Open circuit subtransient T^{\prime\prime}_{q0} 0.046
Armature dc component time constant data
Three-phase short circuit T_{a3} 0.330
Line-to-line short circuit T_{a2} 0.330
Line-to-neutral short circuit T_{a1} 0.294

Related Answered Questions