The effect of motors is neglected in Example 8.3. Calculate the partial currents from the motors at 13.8 kV. Do these motor contributions need to be considered in IEC calculations for a fault at F2? Also, calculate the peak current and the asymmetrical breaking current for a fault at F3 on the 4.16 kV bus.
Effect of Motor Contribution at 13.8 kV Bus, Fault F2
For a fault at the 13.8 kV bus F2, an equivalent impedance of the motors through transformers and cables is calculated. The partial currents from medium- and low-voltage motors are calculated in Tables 8.10 and 8.11, respectively. The equivalent impedance of low-voltage motors of two identical groups, from Table 8.11, is 6.45 + j15.235 per unit.
The per unit impedance of transformer T3 from Table 7.13 is 0.639 + j3.780. Therefore, the lowvoltage motor impedance through transformer T3, seen from the 4.16 kV bus, is 7.089 + j19.015 per unit.
From Table 8.10, the equivalent impedance of medium-voltage motors is 0.58 + j4.55 pu. The equivalent impedances of low- and medium-voltage motors in parallel are
(7.089 + j19.015) || (0.58 + j4.55) = 0.637 + j3.707
To this, add the impedance of cable C1 and transformer T2 from Table 7.13, which gives 0.701 + j4.606 pu. This is the equivalent impedance as seen from the 13.8 kV bus. Thus, the initial short-circuit current from the motor contribution is 1.1/(0.701 + j4.606) per unit = |0.99| kA.
The effect of motors in this example can be ignored, and the above calculation of currents from motor contributions is not necessary. From Equation 8.33,
\frac{ΣP_{rM}}{ΣS_{rT}}≤ \frac{0.8}{|\frac{c100 ΣS_{r\overline{T}}}{S^{\prime \prime}_{kQ} – \ 0.3}|} (8.33)
ΣP_{rm} = sum of the active powers of all medium- and low-voltage motors = 0.86 MW. Also, ΣS_{rT} = rated apparent power of the transformer = 7.5 MVA. The left-hand side of Equation 8.33 = 0.1147. Symmetrical short-circuit power at the point of connection, without effect of motors, is
S^{\prime \prime}_{kQ} = \sqrt{3} I^{\prime \prime}_{k}U_{n} = \sqrt{3} (56.5)(13.8) = 1350.7 \ MVA
The right-hand side of Equation 8.33 gives 2.571, and the identity in Equation 8.33 is satisfied. The effect of motors can be ignored for a fault at 13.8 kV.
If the calculation reveals that motor contributions should be considered, we have to modify i_{p} at the fault point. This requires calculation of χ, which is not straightforward. High-voltage motors have χ = 1.75 or 1.65, and low-voltage motors have χ = 1.65. For a combination load, χ = 1.7 can be used to calculate i_{p} approximately.
Three-phase short-circuit at F3. For a fault at F3, we will first calculate the motor contributions. The low-voltage motor impedance plus transformer T3 impedance is 7.089 + j19.015, as calculated above. The initial short-circuit contribution from the low-voltage motor contribution is 1.1/(7.089 + j19.015) = 0.019 – j0.051 pu or | I^{\prime \prime}_{k}| = 0.76 kA. Medium-voltage impedance, from Table 8.10, is 0.58 + j4.55 per unit. The medium-voltage motor contribution is 0.028- j0.239 pu or | I^{\prime \prime}_{k}| = 3.43 kA.
To calculate the generator and utility source contributions, the impedances Z_{G,PSU} are in || with (Z_{T,PSU} + Z_{Q}), i.e., 0.0074 + j0.1483 in || with 0.006074 + j0.16378. This gives 0.0034 + j0.0778 pu. Add transformer T2 impedance (0.06349 + j0.89776) and cable C1 impedance (0.00038 + j0.00101) from Table 7.13. This gives an equivalent impedance of 0.0673 + j0.976 per unit. Thus, the initial short-circuit current is 0.077 – j1.122 per unit or | I^{\prime \prime}_{k}| = 15.61 kA. The total initial symmetrical
current, considering low- and medium-voltage motor contributions, is 19.80 kA. To calculate i_{p}, χ must be calculated for the component currents.
For contribution through transformer T2, using Equation 8.4:
χ= 1.02 + 0.98e^{-3R/X} (8.4)
χ_{AT} = 1.02 + 0.98ε^{-3(0.06895)}
= 1.82
As this is calculated from a meshed network, a safety factor of 1.15 is applicable, i.e., χ = 1.15 multiplied by 1.82 = 2.093. However, for high-voltage systems, χ is not > 2.0. This gives i_{pAT} = (2)( \sqrt{2} )(15.65) = 44.27. For medium-voltage motors, χ can be calculated from Table 8.10:
χ_{MV} =\frac{ i_{p}}{ \sqrt{2} I^{\prime \prime}_{k}}= \frac{7.39}{ \sqrt{2}(3.06)} = 1.71
For low-voltage motors through transformer T3:
χ_{LVT} = 1.02 + 0.98e^{-3(6.97/19.02)} = 1.346
i_{pLV} = (1.346)( \sqrt{2} )(0.76) = 1.45 \ kA
Total peak current by summation = (44.27 +7.39 + 1.45) = 53.11 kA.
The breaking current is the summation of individual breaking currents:
Breaking current through transformers at 4.16 kV = | I^{\prime \prime}_{k}| = 15.65 kA
Breaking current medium-voltage motors from Table 8.10 = 1.78 kA
For low-voltage motors with I^{\prime \prime}_{KM}/I_{RM} = 6.6, μ = 0.78, q can be conservatively calculated for m ≤ 0.3 and p = 2. This gives q = 0.64. The component breaking current from low-voltage motors is therefore, 0.78 × 0.64 × 0.76 = 0.38 kA. Total symmetrical breaking current = 17.81 kA.
To calculate the asymmetrical breaking current, the dc components of the currents should be calculated:
The dc component of the low-voltage motor contribution is practically zero.
The dc component of the medium-voltage motors at contact parting time of 0.05 s = 0.5 kA.
The dc component of current through transformer T2 = 6.07 kA.
Total dc current at contact parting time = 6.57 kA; this gives asymmetrical breaking current of 18.98 kA.
The results are shown in Table 8.8.
TABLE 8.10 Partial Short-Circuit Currents from Asynchronous Medium-Voltage Motors: Example 8.4 |
||||
Parameter | 2425 hp | 300 hp | 500 hp | Sum (Σ) |
Power output, P_{rm} (MW) | 1.81 | 0.224 | 0.373 | |
Quantity | 1 | 3 | 2 | |
Power factor (cos \phi) | 0.93 | 0.92 | 0.92 | |
Efficiency (η_{r}) | 0.96 | 0.93 | 0.94 | |
Ratio, locked rotor current to full load current (I_{LR}/I_{rM}) |
6 | 6 | 6 | |
Pair of poles (p) | 1 | 1 | 2 | |
Sum of MVA (S_{rM}) | 2.03 | 0.78 | 0.86 | |
Sum, rated current (I_{rM}) | 0.28 | 0.11 | 0.12 | |
I^{\prime \prime}_{K}/I_{rM} | 6.6 | 6.6 | 6.6 | |
Power per pole pair (m) | 1.81 | 0.223 | 0.186 | |
R_{M}/X_{M} | 0.10 | 0.15 | 0.15 | |
κ_{m} | 1.75 | 1.65 | 1.65 | |
μ | 0.78 | 0.78 | 0.78 | |
q | 0.86 | 0.61 | 0.59 | |
I^{\prime \prime}_{KM} | 1.68 | 0.66 | 0.72 | Σ = 3.06 |
i_{pM} | 4.18 | 1.54 | 0.67 | Σ = 7.39 |
i_{bm} | 1.13 | 0.32 | 0.33 | Σ = 1.78 |
Z_{M} (pu) | 8.23 | 21.41 | 1.42 | |
X_{M} (pu) | 0.995 Z_{M} = 8.189 | 0.989 Z_{M} = 21.17 | 0.989 Z_{M} = 19.21 | |
R_{M} (pu) | 0.1 X_{M} = 0.82 | 0.15 X_{M} = 3.18 | 0.15 X_{M} = 2.88 | |
Cable C2 | 0.068 + j0.104 | |||
Σ MV motors and cable | 0.58 + j4.55 |
TABLE 8.11 Low-Voltage Motors, Partial Short-Circuit Current Contributions: Example 8.4 |
|||
Parameter | Motors M4, M5, and M6 (or Identical Group of Motors M40 , M50 , and M6) | Remarks | |
P_{rm} (MW) | 0.43 | Calculated active power rating of the motor group |
|
Sum of MVA (S_{rM}) | 0.52 | Active power rating divided by power factor |
|
R_{M}/X_{M} | 0.42 | From Equation 8.20
\frac{R_{M}}{X_{M}} = 0.10 with X_{M} = 0.995 Z_{M} for high-voltage motors with powers [/latex]P_{rM}[/latex] per pair of poles 1 ≥ MW for group of motors connected through cables |
|
χ_{m} | 1.3 | From Equation 8.4 x = 1.02 + 0.98e^{-3R/X} (8.4) |
|
Ratio, locked rotor current to full load current (I_{LR}/I_{rM}) | 6 | ||
Z_{M} in per unit 100 MVA base | 32.12 | ||
X_{M} in per unit 100 MVA base | 0.922 Z_{M} = 29.61 | Equation 8.20 | |
R_{M} in per unit 100 MVA base | 0.42 X_{M} = 12.44 | Equation 8.20 | |
Cables C3 or C4 in per unit 100 MVA base | 0.46 + j0.860 | Table 7.13 |
TABLE 7.13 Impedance Data (Example 7.2) |
||||||
Description of Equipment | Per Unit Resistance on a 100 MVA Base | Per Unit Reactance on a 100 MVA Base | ||||
Utility’s 138 kV source, three-phase fault level = 4556 MVA, X/R ratio = 13.4 | 0.00163 | 0.02195 | ||||
112.1 MVA generator, saturated sub transient = 16.4% data in Table 6.1 | 0.001133 | 0.14630 | ||||
Transformer T_{1}, 60/100 MVA, Z = 7.74%, X/R = 32 | 0.00404 | 0.12894 | ||||
Transformer T_{3}, 1.5 MVA, Z = 5.75%, X/R = 5.9% | 0.06349 | 0.89776 | ||||
Transformer T_{2}, 7.5 MVA, Z = 6.75%, X/R = 14.1 | 0.63909 | 3.77968 | ||||
3.8 kV cable C_{1}, 2-1/C per phase, 1000 KCMIL, in steel conduit, 80 ft | 0.00038 | 0.00101 | ||||
4.16 kV cable C_{2}, 1-1/C per phase, 500 KCMIL, in steel conduit, 400 ft | 0.06800 | 0.10393 | ||||
0.48 kV cables C_{3} and C_{4}, 3-1/C per phase, 750 KCMIL, in steel conduit, 150 ft | 0.46132 | 0.85993 | ||||
M_{1}, 2425 hp, 2-pole induction motor | 0.23485 | 7.6517 | ||||
M_{2}, 300 hp, 2-pole induction motors, 3 each | 1.2997 | 19.532 | ||||
M_{3}, 500 hp, 2-pole induction motors, 2 each | 0.90995 | 17.578 | ||||
M_{4} and M^{\prime}_{4}, 150 hp, 4-pole induction motor | 11.714 | 117.19 | ||||
M_{5} and M^{\prime}_{5}, 75 hp, 4-pole, induction motor, 3 each | 10.362 | 74.222 | ||||
M_{6} and M^{\prime}_{6}, 200 hp induction motors, lumped, < 50 hp | 20.355 | 83.458 | ||||
B_{1}, 5 kA bus duct, phase-segregated, 40 ft | 0.0005 | 0.00004 | ||||
B_{2}, 5 kA bus duct, phase-segregated, 80 ft | 0.00011 | 0.00008 |
TABLE 8.8 Examples 8.3 and 8.4: Comparative Results of Three-Phase Short-Circuit Calculations |
|||
Fault Location | Calculation Method | First-Cycle Current kA asym. Peak (ANSI) or Peak Current i_{p} (IEC) | Interrupting Duty Current (ANSI) or I_{basym}(IEC) |
Fl (138 kV) | ANSI calculation IEC calculation |
53.1 57.53 |
20.54 × 1.2 = 24.65 (Example 7.2) 26.47 |
F2(13.8 kV) | ANSI calculation IEC calculation |
155.69 147.61 |
71.69 × 1.1 = 78.86 (Example 7.3) 74.21 |
F3 (4.16 kV) | ANSI calculation IEC calculation |
46.23 53.11 |
16.35 × 1.1 = 17.99 (Note) 18.98 |
Note: Not calculated in chapter 7, a reader can verify the calculations shown.
TABLE 6.1 | ||
Generator Data | ||
Description | Symbol | Data |
Generator 112.1 MVA, 2-pole, 13.8 kV, 0.85 PF, 95.285 MW, 4690 A, 0.56 SCR, 235 field V, wye connected |
||
Per unit reactance data, direct axis | ||
Saturated synchronous | X_{dv} | 1.949 |
Unsaturated synchronous | X_d | 1.949 |
Saturated transient | X^\prime_{dv} | 0.207 |
Unsaturated transient | X^\prime_d | 0.278 |
Saturated subtransient | X^{\prime\prime}_{dv} | 0.164 |
Unsaturated subtransient | X^{\prime\prime}_{d} | 0.193 |
Saturated negative sequence | X_{2\text{v}} | 0.137 |
Unsaturated negative sequence | X_{2I} | 0.185 |
Saturated zero sequence | X_{0\text{v}} | 0.092 |
Leakage reactance, overexcited | X_{0I} | 0.111 |
Leakage reactance, underexcited | X_{LM,OXE} | 0.164 |
X_{LM,UXE} | 0.164 | |
Per unit reactance data, quadrature axis | ||
Saturated synchronous | X_{q\text{v}} | 1.858 |
Unsaturated synchronous | X_q | 1.858 |
Unsaturated transient | X^\prime_q | 0.434 |
Saturated subtransient | X^{\prime\prime}_{q\text{v}} | 0.140 |
Unsaturated subtransient | X^{\prime\prime}_{q} | 0.192 |
Field time constant data, direct axis | ||
Open circuit | T^\prime_{d0} | 5.615 |
Three-phase short-circuit transient | T^\prime_{d3} | 0.597 |
Line-to-line short-circuit transient | T^\prime_{d2} | 0.927 |
Line-to-neutral short-circuit transient | T^\prime_{d1} | 1.124 |
Short-circuit subtransient | T^{\prime\prime}_{d} | 0.015 |
Open circuit subtransient | T^{\prime\prime}_{d0} | 0.022 |
Field time constant data quadrature axis | ||
Open circuit | T^\prime_{q0} | 0.451 |
Three-phase short-circuit transient | T^\prime_{q} | 0.451 |
Short-circuit subtransient | T^{\prime\prime}_{q} | 0.015 |
Open circuit subtransient | T^{\prime\prime}_{q0} | 0.046 |
Armature dc component time constant data | ||
Three-phase short circuit | T_{a3} | 0.330 |
Line-to-line short circuit | T_{a2} | 0.330 |
Line-to-neutral short circuit | T_{a1} | 0.294 |