A balanced three-phase load requires 480 kW at a lagging power factor of 0.8. The load is fed from a line having an impedance of 0.005 + j0.025 Ω/Φ . The line voltage at the terminals of the load is 600 V.
a) Construct a single-phase equivalent circuit of the system.
b) Calculate the magnitude of the line current.
c) Calculate the magnitude of the line voltage at the sending end of the line.
d) Calculate the power factor at the sending end of the line.