The primary, secondary and tertiary windings of a 50-Hz, single-phase, 3-winding transformer are rated as 6.35 kV, 5 MVA; 1.91 kV, 2.5 MVA; 400 V, 2.5 MVA respectively. Three SC tests on this transformer yielded the following results:
(i) Secondary shorted, primary excited: 500 V, 393.7 A
(ii) Tertiary shorted, primary excited: 900 V, 393.7 A
(iii) Tertiary shorted, secondary excited: 231 V, 21 312.1 A
Resistances are to be ignored.
(a) Find the pu values of the equivalent circuit impedances of the transformer on a 5 MVA, rated voltage
base.
(b) Three of these transformers are used in a 15 MVA, Y-Y-\Delta , 3-phase bank to supply 3.3 kV and 400 V auxiliary power circuits in a generating plant. Calculate the pu values of steady-state short-circuit currents and of the voltage at the terminals of the secondary windings for a 3-phase balanced shortcircuit at the tertiary terminals. Use 15 MVA, 3-phase rated voltage base.