Question 3.26: A 440/220 V single-phase transformer has percentage resistan...

A 440/220 V single-phase transformer has percentage resistance drop and reactance drop of 1.2 per cent and 6 per cent, respectively. Calculate the voltage regulation of the transformer at 0.8 power factor lagging.

The blue check mark means that this solution has been answered and checked by an expert. This guarantees that the final answer is accurate.
Learn more on how we answer questions.

Percentage voltage regulation    =\frac{(I_{2}  R^{′′}_{e} \cos Φ  +  I_{2}  X^{′′}_{e} \sin Φ)  }{E_{2}} ×  100

 

= \frac{ I_{2}  R^{′′}_{e} }{ E_{2}} \cos Φ  ×   100 + \frac{ I_{2}  X^{′′}_{e} }{ E_{2}} \sin Φ  ×   100.

Given,                                        \frac{ I_{2}  R^{′′}_{e} }{ E_{2}}  ×   100 = 1.2, \frac{ I_{2}  X^{′′}_{e} }{ E_{2}}  ×   100 = 6.0,  \cos Φ = 0.8

 

\sin Φ = 0.6.

Substituting values regulation                  = \frac{ I_{2}  R^{′′}_{e} }{ E_{2}}  \cos Φ  + \frac{ I_{2}  X^{′′}_{e} }{ E_{2}} \sin Φ

= 1.2 ×.0.8 + 6.0 × 0.6
= 4.56 per cent