A 3 MVA, 6600 V, three-phase, star connected synchronous generator has a resistance of 0.2 Ω and synchronous reactance of 3.5 Ω per phase. Calculate the regulation at rated output at 0.8 power factor lagging. The speed and excitation remain constant.

The blue check mark means that this solution has been answered and checked by an expert. This guarantees that the final answer is accurate.
Learn more on how we answer questions.

Given line voltage = 6600 V

phase voltage  V_{Ph} = \frac{6600}{\sqrt{3}}

= 3810 V

R_{a} = 0.2  Ω
X_{s} = 3.5  Ω, \cos Φ = 0.8 lagging, \sin Φ = 0.6
Total MVA = 3
Total VA = 3 × 10^{6}
This VA is for the three phases. VA per phase will be one-third of the total VA
VA per phase = 1 × 10^{6}

Current per phase   I_{a} = \frac{1  ×  10^{6}}{V_{Ph}} = \frac{10,00,000}{3,810} = 262.5  A

Induced EMF,      E = \sqrt{( V \cos Φ  +  I_{a}  R_{a})²  +  ( V \sin Φ  +  I_{a}  X_{S} )² }

 

= \sqrt{(3810 × 0.8 + 262.5 × .2)²  +  (3810 × 0.6 + 262.5 × 3.5)²}

= 4049.4 V

Percentage regulation  = \frac{(E  –  V)}{V} × 100 = \frac{(4049.4  –  3810)}{3810} × 100 = 6.28 per cent

4.54