Question 4.18: A 1500 kVA, 3300V, 50Hz, three-phase, star-connected synchro...
A 1500 kVA, 3300V, 50Hz, three-phase, star-connected synchronous generator has an armature resistance of 0.2 Ω per phase. A field current of 50 A produces a short-circuit current of 262 A and an open-circuit EMF of 1200 V between the lines. Calculate voltage regulation of the generator on full load at 0.8 power factor lagging and at 0.8 power factor leading.
Learn more on how we answer questions.
Total kVA = 1500
kVA per phase = \frac{1500}{3} = 500
Per-phase voltage = \frac{V_{L}}{\sqrt{3}} = \frac{3300}{\sqrt{3}} V = 1905 V
Per-phase current, I_{a} = \frac{500 × 1000}{3300 / \sqrt{3}} = 262 A
Given that at a field current of 50 A, short circuit I_{a} is 262 A and the open-circuit line voltage is 1200 V
Synchronous impedance/phase Z_{s} = \frac{open – circuit voltage per phase}{short – circuit current} = \frac{1200}{\sqrt{3} × 262} = 2.64 Ω
R_{a} per phase = 0.2 Ω
\cosΦ = 0.8, Φ = 37°, \sinφ = 0.6At lagging power factor load
E_{1} = \sqrt{(V \cos Φ + I_{a} R_{a})² + (V \sin Φ + I_{a} X_{s})²}and at leading power factor load
E_{2} = \sqrt{(V \cos Φ + I_{a} R_{a})² + (V \sin Φ – I_{a} X_{s})²}
= 2418 V
Percentage regulation at full load 0.8 power factor lagging
= \frac{(2418 – 1905) × 100}{1905} = 26.9 per cent
=1640 V
Percentage regulation at full load 0.8 power factor leading
\frac{ E_{2} – V}{1905} × 100 = \frac{ (1640 – 1905)}{1905} × 100 = – 13.9 per cent.
This shows that regulation is negative at 0.8 leading power factor load. This is because the full-load terminal voltage is more than the no-load voltage.