Question 9.2: A house has a winter heating requirement of 30 kJ.s^−1 and a...

A house has a winter heating requirement of 30  kJ⋅s^{−1} and a summer cooling requirement of 60  kJ⋅s^{−1}. Consider a heat pump installation to maintain the house temperature at 20°C in winter and 25°C in summer. This requires circulation of the refrigerant through interior exchanger coils at 30°C in winter and 5°C in summer. Underground coils provide the heat source in winter and the heat sink in summer. For a year-round ground temperature of 15°C, the heat-transfer characteristics of the coils necessitate refrigerant temperatures of 10°C in winter and 25°C in summer. What are the minimum power requirements for winter heating and summer cooling?

The blue check mark means that this solution has been answered and checked by an expert. This guarantees that the final answer is accurate.
Learn more on how we answer questions.

The minimum power requirements are provided by a Carnot heat pump. For winter heating, the house coils are at the higher-temperature level   T_H   , and the heat requirement is   QH = 30  kJ⋅s^{−1}   . Application of Eq. (5.4) gives:

\frac{-Q_C}{T_C}=\frac{Q_H}{T_H}           (5.4)

Q_C=-Q_H \frac{T_C}{T_H}=30\left(\frac{10+273.15}{30+273.15}\right)=28.02 \mathrm{~kJ} \cdot \mathrm{s}^{-1}

This is the heat absorbed in the ground coils. By Eq. (9.1),

W=-\left(Q_C+Q_H\right)           (9.1)

W=-Q_H-Q_C=30-28.02=1.98 \mathrm{~kJ} \cdot \mathrm{s}^{-1}

Thus the power requirement is 1.98 kW.

For summer cooling, Q_C=60 \mathrm{~kJ} \cdot \mathrm{s}^{-1} , and the house coils are at the lowertemperature level T_C . Combining Eqs. (9.2) and (9.3) and solving for W:

\omega \equiv \frac{\text { heat absorbed at the lower temperature }}{\text { net work }}=\frac{Q_C}{W}            (9.2)

\omega=\frac{T_C}{T_H-T_C}            (9.3)

W=Q_C \frac{T_H-T_C}{T_C}=60\left(\frac{25-5}{5+273.15}\right)=4.31 \mathrm{~kJ} \cdot \mathrm{s}^{-1}

The power requirement here is therefore 4.31 kW. Actual power requirements for practical heat pumps are likely to be more than twice this lower limit.