Chapter 13

Q. 13.2

A counterflow spray dehumidifier is to be designed as shown schematically in Fig. 13-5. These are the design conditions:

t_{l2} = 7 C Water temperature at the inlet
t_{l1} = 15 C Water temperature at the outlet
t_{a1} = 28 C Air dry bulb temperature at the inlet
t_{wb1} = 22 C Air wet bulb temperature at the inlet
G_{a} = 1.36 kg/(s-m²) Air mass flow rate per unit area
G_{l} c_{l}/G_{a} = 3.25 Spray ratio
h_{a}  a_{h} = 1210 W/(C-m³) Air heat-transfer coefficient per unit volume
h_{l}  a_{h} = 14,700 W/(C-m³) Liquid heat-transfer coefficient per unit volume
Q = 2.83 m³/s Air volume flow rate

Find the cross-sectional area and final state of the air.

13.5

Step-by-Step

Verified Solution

The mass flow rate of the dry air is given by

\dot{m}_{a}  =  \frac{\dot{Q}}{v_{1}}  =  \frac{2.83}{0.875}  =  3.24   kg/s

The chamber cross-sectional area is then

A_c  =  \frac{\dot{m}_{a} }{G_{a}}  =  \frac{3.24}{1.36}  =  2.38  m^{2}

Using the Colburn analogy and assuming that a_{m}  =  a_{h},

h_{d} a_{m}  =  \frac{h_{a} a_{m}}{c_{pa}}  =  \frac{1210}{1000}  =  1.21 kg/(s-m³)

The graphical solution for the interface states and the process path is shown in Fig.13-6. In the case of counterflow, the air entering at 28 C is in contact with the water at 15 C, and the air leaving is in contact with the water at 7 C. The procedure is quite similar to that given in Example 13-1. Note, however, that the energy balance line AB has a positive slope because of the counterflow arrangement. Notice also that because of counterflow, point A corresponds to t_{l1}  and  point  B  corresponds  to  t_{l2}. The final state of the air is defined by t_{a2}  =  14  C  and  t_{wb2} = 13.5 C.

The height of the spray chamber is determined by using Eq. 13-22b with the procedure given in Example 13-1.

G_{a}  d_{i}  =  h_{d} a_{m}  (i_{i}  –  i)dL                  (13-22b)

13.6