Question 9.CSGP.134: Find the isentropic efficiency for the compressor in Problem......

Find the isentropic efficiency for the compressor in Problem 6.57.
A compressor in an air-conditioner receives saturated vapor R-410a at 400 kPa and brings it to 1.8 MPa, 60°C in an adiabatic compression. Find the flow rate for a compressor work of 2 kW?

Step-by-Step
The 'Blue Check Mark' means that this solution was answered by an expert.
Learn more on how do we answer questions.

C.V. Actual Compressor, assume adiabatic and neglect kinetic energies.
Energy Eq.6.13:      w = h _1- h _2

Entropy Eq.9.9:        s _2= s _1+ s _{ gen }

States: 1: B.4.2    h _1=271.9\, kJ / kg , \quad s _1=1.0779 \,kJ / kg – K

2: B.4.2      h _2=323.92 \,kJ / kg

– w _{ C }= h _2- h _1=323.92-271.9=52.02 \,kJ / kg

Ideal compressor. We find the exit state from (P,s).
State 2s:      P _2, s _{2 s }= s _1=1.0779 \,kJ / kg – K \Rightarrow h _{2 s }=314.33 \,kJ / kg

– w _{ Cs }= h _{2 s }- h _1=314.33-271.9=42.43\,kJ / kg

\eta_{ C }=- w _{ C s } /- w _{ C }=\frac{42.43}{52.02}= 0 . 8 1 6