The inductive load ZL in Figure 16–10 draws an apparent power of 5 kVA at a lagging power factor of 0.75 when the load voltage is 1.2 kV (rms) at 60 Hz. Find the power factor of the parallel combination when C = 5 μF.
For |SL| = 5 kVA at a lagging power factor of 0.75, the complex power delivered to ZL is
S_{L} = 5000 × (0.75 + j\sqrt{1 – 0.75^{2}})
When |VL| = 1200 V(rms) at 60 Hz, the reactive power of a 5-μF capacitor is
QC = −2πfC|VL|² = −2π60 × 5 × 10-6(1200)²
= −2714 VAR
The total complex power delivered to the parallel combination is
SP = SL + jQC − 3750 + j3307 − j2714
= 3750 + j593 VA
and the “corrected” power factor of the parallel combination is
pf_{cor} = \frac{3750}{|3750 + j593|} = 0.988