Holooly Plus Logo

Question 24.2: Use of the Solar Load Ratio Method Find the auxiliary heatin......

Use of the Solar Load Ratio Method

Find the auxiliary heating energy for the building of Figure 24.7 in Denver, Colorado, in January.

Given: T_{i} = 68°F (20°C)

\dot{Q}_{gain} = 4200  Btu/h (1231  W)

Sunspace design type D1 (12 in. [0.3 m] masonry wall between sunspace and conditioned space)

Sunspace being unconditioned and Semienclosed by conditioned space
Aperture of sunspace double glazed with an area of 550 ft² (51.1 m²), its normal being tilted at 50° from vertical
South facing, without night insulation

The envelope has the following characteristics:

The heat loss coefficient without the sunspace is indicated in italic as 525.0 Btu/(h· °F) (277 W/K).
Hence, the NLC is
NLC = 24  h/day \times 525.0  Btu/(h \cdot °F)

= 12,600  Btu/(°F . day)
Find: Q_{aux}
Lookup values: We need to look up solar radiation S and degree-days D_{h} for January in Denver.
(For simplicity, we take these values as known; they could be calculated by using the methods of Sections 4.9 and 10.3.)
S = 43,600 Btu/ft²
= Monthly solar radiation on aperture
For the degree-days, we first determine the balance-point temperature from Equation 24.3:

T_{bal} = T_{i}  –  \frac{\dot{Q}_{gain,day}}{NLC}            (24.3)
T_{bal} = 68°  –  \frac{24  h  \times  4,200  Btu/h}{12,600  Btu/(°F \cdot day)} = 60°F
The corresponding degree-days are

D_{h} = 930°F \cdot days

= Monthly degree-days D_{h}(T_{bal})  for base T_{bal}

A or \dot{V},ft^{2} or ft³/min U, Btu/ (h· °F·ft²) UA or \rho c_{p} \dot{V}, Btu/(h· °F)
Opaque walls 2,000 0.040 80.0
Roof 3,000 0.030 90.0
Floor (over
crawl space)
3,000 0.040 120.0
Windows (east,
west, north)
100 0.550 55.0
Subtotal 345.0
Infiltration 200 ft³/min (at 0.5 ach with V = 24,000 ft³) \rho c_{p} = 0.015 Btu/(ft³ · °F) in Denver 180.0
Subtotal 525.0
Sunspace 550 0.55 302.2
Total 827.2
24.7
Step-by-Step
The 'Blue Check Mark' means that this solution was answered by an expert.
Learn more on how do we answer questions.

The projected area is

A_{proj} = 550  ft^{2} \times \sin 50° = 421  ft^{2}

From Equation 24.4,

LCR = \frac{NLC}{A_{proj}}              (23.4  IP)

LCR = \frac{12,600  Btu/(°F \cdot day \cdot ft^{2})}{421  ft^{2}} = 29.9  Btu/(°F \cdot day)

For the ratio S/D_{h}, we have

\frac{S}{D_{h}} = \frac{43.600  Btu/ft^{2}}{930°F \cdot day} = 46.9  Btu/(°F \cdot day \cdot ft^{2})

Reading Figure 24.8 at these values, we find
SSF = 0.51
This means that 51% of the heating requirement of the building is provided by the sunspace in January. Equation 24.5 yields the auxiliary heating requirement for the month:

Q_{aux} = NLC \times D_{h} \times (1  –  SSF)            (24.5)

\dot{Q}_{aux} = NLC \times D_{h} \times (1  –  SSF)

= 12,600 Btu/(°F . day) × 930 °F . days × (1  –  0.51)

= 5.74  MBtu/month

Comments
In accordance with the assumptions of the method, this result presupposes that the thermostat dead band is 65°F–75°F for the conditioned part of the building and 45°F–95°F for the sunspace. The designer should check whether this is agreeable with the future occupants of the building

24.8

Related Answered Questions