Use of the Solar Load Ratio Method
Find the auxiliary heating energy for the building of Figure 24.7 in Denver, Colorado, in January.
Given: T_{i} = 68°F (20°C)
\dot{Q}_{gain} = 4200 Btu/h (1231 W)Sunspace design type D1 (12 in. [0.3 m] masonry wall between sunspace and conditioned space)
Sunspace being unconditioned and Semienclosed by conditioned space
Aperture of sunspace double glazed with an area of 550 ft² (51.1 m²), its normal being tilted at 50° from vertical
South facing, without night insulation
The envelope has the following characteristics:
The heat loss coefficient without the sunspace is indicated in italic as 525.0 Btu/(h· °F) (277 W/K).
Hence, the NLC is
NLC = 24 h/day \times 525.0 Btu/(h \cdot °F)
= 12,600 Btu/(°F . day)
Find: Q_{aux}
Lookup values: We need to look up solar radiation S and degree-days D_{h} for January in Denver.
(For simplicity, we take these values as known; they could be calculated by using the methods of Sections 4.9 and 10.3.)
S = 43,600 Btu/ft²
= Monthly solar radiation on aperture
For the degree-days, we first determine the balance-point temperature from Equation 24.3:
T_{bal} = T_{i} – \frac{\dot{Q}_{gain,day}}{NLC} (24.3)
T_{bal} = 68° – \frac{24 h \times 4,200 Btu/h}{12,600 Btu/(°F \cdot day)} = 60°F
The corresponding degree-days are
= Monthly degree-days D_{h}(T_{bal}) for base T_{bal}
A or \dot{V},ft^{2} or ft³/min | U, Btu/ (h· °F·ft²) | UA or \rho c_{p} \dot{V}, Btu/(h· °F) | |
Opaque walls | 2,000 | 0.040 | 80.0 |
Roof | 3,000 | 0.030 | 90.0 |
Floor (over crawl space) |
3,000 | 0.040 | 120.0 |
Windows (east, west, north) |
100 | 0.550 | 55.0 |
Subtotal | 345.0 | ||
Infiltration | 200 ft³/min (at 0.5 ach with V = 24,000 ft³) | \rho c_{p} = 0.015 Btu/(ft³ · °F) in Denver | 180.0 |
Subtotal | 525.0 | ||
Sunspace | 550 | 0.55 | 302.2 |
Total | 827.2 |
The projected area is
A_{proj} = 550 ft^{2} \times \sin 50° = 421 ft^{2}From Equation 24.4,
LCR = \frac{NLC}{A_{proj}} (23.4 IP)
LCR = \frac{12,600 Btu/(°F \cdot day \cdot ft^{2})}{421 ft^{2}} = 29.9 Btu/(°F \cdot day)For the ratio S/D_{h}, we have
\frac{S}{D_{h}} = \frac{43.600 Btu/ft^{2}}{930°F \cdot day} = 46.9 Btu/(°F \cdot day \cdot ft^{2})Reading Figure 24.8 at these values, we find
SSF = 0.51
This means that 51% of the heating requirement of the building is provided by the sunspace in January. Equation 24.5 yields the auxiliary heating requirement for the month:
Q_{aux} = NLC \times D_{h} \times (1 – SSF) (24.5)
\dot{Q}_{aux} = NLC \times D_{h} \times (1 – SSF)= 12,600 Btu/(°F . day) × 930 °F . days × (1 – 0.51)
= 5.74 MBtu/month
Comments
In accordance with the assumptions of the method, this result presupposes that the thermostat dead band is 65°F–75°F for the conditioned part of the building and 45°F–95°F for the sunspace. The designer should check whether this is agreeable with the future occupants of the building