Question 2.45: A three-phase star-connected load consumes a total of 12 kW ...

A three-phase star-connected load consumes a total of 12 kW at a power factor of 0.8 lagging when connected to a 400 V, three phase, 50 Hz power supply. Calculate the resistance and inductance of load per phase.

The blue check mark means that this solution has been answered and checked by an expert. This guarantees that the final answer is accurate.
Learn more on how we answer questions.

Total power consumed = 12 kW
Per phase power consumed = 4 kW
So,                                              V_{Ph}  I_{Ph} \cosΦ = 4000  W

I_{Ph}=\frac{4000}{V_{Ph} \cosΦ}

or,                          I_{Ph}=\frac{4000}{(400 / \sqrt{3})  ×  0.8} =21.6  A

I_{Ph}=\frac{  V_{Ph}}{  Z_{Ph}}

Z_{Ph}=\frac{ V_{Ph}}{ I_{Ph}}= \frac{231}{21.6}=10.7  Ω.      Power factor,   \cos Φ = 0.8,     \sin Φ= 0.6

R = Z_{Ph} \cosΦ = 10.7  ×  0.8 = 8.56  Ω
X = Z_{Ph} \sin Φ = 10.7  ×  0.6 = 6.42  Ω

X = 6.42
2π fL = 6.42

L =\frac{6.42}{2  ×  3.14  ×  50}=20.4  ×  10^{-3} H

= 20.4  mH