Question 11.7: Assume that a bank of heating resistors is rated at 28 kW an...
Assume that a bank of heating resistors is rated at 28 kW and is connected to 240 V. The resistors operate for more than three hours at a time and are located in an area with an ambient temperature of 86ºF. Aluminum conductors with Type THWN-2 insulation are to be used to connect the heaters. What size conductors should be used?
The "Step-by-Step Explanation" refers to a detailed and sequential breakdown of the solution or reasoning behind the answer. This comprehensive explanation walks through each step of the answer, offering you clarity and understanding.
Our explanations are based on the best information we have, but they may not always be right or fit every situation.
Our explanations are based on the best information we have, but they may not always be right or fit every situation.
The blue check mark means that this solution has been answered and checked by an expert. This guarantees that the final answer is accurate.
Learn more on how we answer questions.
Learn more on how we answer questions.
Related Answered Questions
Question: 11.8
Verified Answer:
Determine the amount of current needed to operate ...
Question: 11.12
Verified Answer:
The solution to this problem is very similar to th...
Question: 11.9
Verified Answer:
The value for K can be found in the table in Figur...
Question: 11.6
Verified Answer:
Because a motor load is continuous, multiply the f...
Question: 11.5
Verified Answer:
Find the ampacity of a 14 AWG copper conductor wit...
Question: 11.11
Verified Answer:
The first step in the solution of this problem is ...
Question: 11.10
Verified Answer:
To find the size of wire, use
CM = \frac{K ...
Question: 11.13
Verified Answer:
E_{D} = \frac{2 \times 10.4 \Omega-CM/ft...
Question: 11.14
Verified Answer:
E_{D} = \frac{1.732 \times 17 \Omega-CM/...
Question: 11.15
Verified Answer:
Use the formula
R = R_{ref}[1 + \alpha (T...