Question 3.23: Efficiency of 400/200 V, 200 kVA transformer is 98.5 per cen...

Efficiency of 400/200 V, 200 kVA transformer is 98.5 per cent at full load at 0.8 lagging power factor. At half load, 0.8 power factor lagging the efficiency is 97.5 per cent. Calculate the values of core loss and full-load copper loss.

The blue check mark means that this solution has been answered and checked by an expert. This guarantees that the final answer is accurate.
Learn more on how we answer questions.

Let W_{c} be the core loss and W_{cu} be the full-load copper loss.

\eta_{F.L} = 0.985 = \frac{200  ×  0.8}{200  ×  0.8  + W_{c}  +  W_{cu}}

or,                                                          0.985 = \frac{160}{160  +  W_{c}  +  W_{cu}}

or,                                                          \frac{160}{0.985} = 160  +  W_{c}  +  W_{cu}

or,                                                          W_{c}  +  W_{cu} =  2.43  kW = 2430  W                                                                (3.50)

At half load, W_{c} will remain the same but W_{cu} will be one-fourth its full-load value. Efficiency at half load is

\eta_{H.L} = \frac{100  ×  0.8}{100  ×  0.8  + W_{c}  +  (W_{cu}/4)} = \frac{80}{80  +  W_{c}  +  (W_{cu}/4)}

or,                                   0.975 = \frac{320}{320  +  4  W_{c}  +  W_{cu}}

or,                                   \frac{320}{0.975} = 320  +  4  W_{c}  +  W_{cu}

or,                                   4  W_{c} + W_{cu} = 8.2  kW = 8200  W                                                                    (3.51)

From (3.50) and (3.51),                     W_{c} = 1923  W

and                                                         W_{cu} = 507  W