Question 12.18: In a standard vapour compression refrigeration cycle, operat...

In a standard vapour compression refrigeration cycle, operating between an evaporator temperature of – 10°C and a condenser temperature of 40°C, the enthalpy of the refrigerant, Freon-12, at the end of compression is 220 kJ/kg. Show the cycle diagram on T-s plane. Calculate :
(i) The C.O.P. of the cycle.
(ii) The refrigerating capacity and the compressor power assuming a refrigerant flow rate of 1 kg/min. You may use the extract of Freon-12 property table given below :

t(°C) p(MPa) h_{f} (kJ/kg) h_{g} (kJ/kg)
– 10
40
0.2191
0.9607
26.85
74.53
183.1
203.1

(GATE)

The blue check mark means that this solution has been answered and checked by an expert. This guarantees that the final answer is accurate.
Learn more on how we answer questions.

The cycle is shown on T-s diagram in Fig. 29.
Given : Evaporator temperature                          = – 10°C
Condenser temperature                                          = 40°C
Enthalpy at the end of compression,              h_{3} = 220 kJ/kg
From the table given, we have
h_{2}  =    183.1    kJ/kg ;    h_{1}   =    h_{f_4} = 26.85 kJ/kg

(i) The C.O.P. the cycle :

C.O.P. =    \frac{R_{n}}{W}   =    \frac{ h_{2}   –    h_{1}}{ h_{3}   –    h_{2}}

\frac{183.1   –    74.53}{220   –    183.1}   = 2.94 .

(ii) Refrigerating capacity :
Refrigerating capacity                                         = m( h_{2}   –    h_{1} )
[where m = mass flow rate of refrigerant = 1 kg/min …(Given)] )
= 1 × (183.1 – 74.53) = 108.57 kJ/min.

Compressor power :
Compressor power                                    =  m( h_{3}   –    h_{2} )
= 1 × (220 – 183.1) = 36.9 kJ/min     or    0.615 kJ/s

= 0.615 kW.