Question 9.12: No-load test and blocked-rotor test were performed on a 10 h...

No-load test and blocked-rotor test were performed on a 10 hp, four-pole, 400 V, 50 Hz, three-phase induction motor to determine its efficiency. The test data are given as follows:

no-load test:      V = 400 V, I = 6 A, P = 300 W

blocked-rotor test:      V = 40 V, I = 24 A, P = 700 W

Calculate the efficiency of the motor on full load.

The blue check mark means that this solution has been answered and checked by an expert. This guarantees that the final answer is accurate.
Learn more on how we answer questions.

Losses under blocked-rotor test is considered equal to I²R losses in the two windings. If R_{e} is the equivalent resistance of the two windings referred to stator side, then total copper loss

3   I^{2}  R_{e}^{\prime}=700  W

 

R_{e}^{\prime}=\frac{700}{3 \times 24 \times 24}=0.4  \Omega

At no load, I^{2}  R loss in the windings

\begin{aligned}&=3  I_{0}^{2}  R_{e}^{\prime}=3 \times 6^{2} \times 0.4 \\&=43.2  W\end{aligned}

No-load power input = 300 W

Core loss + Frictional and Windage loss = 300 − 43.2

= 256.8 W

Output = 10 hp = 10 × 735.5 = 7355 W

Efficiency,     \eta =\frac{\text { Output }}{\text { Output }+\text { Losses }}=\frac{10 \times 735.5 \times 100}{10 \times 735.5+700+256.8}

= 88.5 per cent