Question 5.9: Power-Factor Correction A50-kW load operates from a 60-Hz 10...

Power-Factor Correction
A50-kW load operates from a 60-Hz 10-kV-rms line with a power factor of 60 percent lagging. Compute the capacitance that must be placed in parallel with the load to achieve a 90 percent lagging power factor.

The blue check mark means that this solution has been answered and checked by an expert. This guarantees that the final answer is accurate.
Learn more on how we answer questions.

First, we find the load power angle:

\theta_L=\mathrm{arccos}\left(0.6\right) =53.13^\circ

Then, we use the power-triangle concept to find the reactive power of the load. Hence,

Q_L=P_L\tan{(\theta_L)}=66.67\mathrm{~kVAR}

After adding the capacitor, the power will still be 50 kW and the power angle will become

\theta_\mathrm{new}=\mathrm{arccos}\left(0.9\right) =25.84^\circ

The new value of the reactive power will be

Q_\mathrm{new}=P_L\tan{(\theta_\mathrm{new})}=24.22\mathrm{~kVAR}

Thus, the reactive power of the capacitance must be

Q_{C}=Q_\mathrm{new}-Q_{L}=-42.45\mathrm{~kVAR}

Now, we find that the reactance of the capacitor is

X_C=-\frac{V^2_{\mathrm{rms}}}{Q_C} =\frac{\left(10^4\right)^2 }{42,450} =-2356~\Omega

Finally, the angular frequency is

\omega=2\pi 60=377.0

and the required capacitance is

C=\frac{1}{\omega\left|X_C\right| }=\frac{1}{377\times 2356} =1.126~\mu\mathrm{F}