Question 7.1: The following currents were recorded under fault conditions ...
The following currents were recorded under fault conditions in a three-phase system:
I_{A} =150\angle 45° A
I_{B} =250\angle 150° A
I_{C} =100\angle 300° A
Calculate the values of the positive, negative, and zero phase sequence components for each line.
The blue check mark means that this solution has been answered and checked by an expert. This guarantees that the final answer is accurate.
Learn more on how we answer questions.
Learn more on how we answer questions.
I_{0} =\frac{1}{3} \left(I_{A}+I_{B}+I_{C}\right)
=\frac{1}{3}\left(106.04+j 106.07 +j106.07 -216.51 +j125.00 +50 -j86.6\right)
=52.2\angle 112.7°
I_{+}=\frac{1}{3}\left(I_{A}+\alpha I_{B}+\alpha ^{2}I_{C} \right)=\frac{1}{3}\left(150\angle 45°+250\angle 270°+100\angle 180°\right)
=48.02\angle -87.6°
I_{-}=\frac{1}{3}\left(I_{A}+\alpha ^{2}I_{B}+\alpha I_{C} \right)
=163.21\angle 40.45°
Related Answered Questions
Question: 7.6
Verified Answer:
The sequence network connection is as shown in Fig...
Question: 7.7
Verified Answer:
The sequence network connection is as shown in Fig...
Question: 7.10
Verified Answer:
The load currents are calculated as follows:
[late...
Question: 7.4
Verified Answer:
The positive sequence network is as shown in Figur...
Question: 7.9
Verified Answer:
The primary line current is given by
I_{P} ...
Question: 7.8
Verified Answer:
I_{A_{sc} }=I_{+}=\frac{1\angle 0}{j\left(0...
Question: 7.5
Verified Answer:
The sequence networks are connected in series for ...
Question: 7.2
Verified Answer:
V_{A}=V_{+}+V_{-}+V_{0}
=200...
Question: 7.3
Verified Answer:
The zero sequence network is shown in Figure 7.16.