Question 32.8: The following results were obtained on a 50 kVA transformer....
The following results were obtained on a 50 kVA transformer. Opencircuit test – primary voltage, 3300 V; secondary voltage, 400 V; primary power, 430 W. Short-circuit test – primary voltage, 124 V; primary current, 15.3 A; primary power, 525 W; secondary current, full-load value. Calculate:
(a) the efficiencies at full load and at half load for 0.7 power factor;
(b) the voltage regulations for power factor 0.7, (i) lagging, (ii) leading;
(c) the secondary terminal voltages corresponding to (i) and (ii).
The "Step-by-Step Explanation" refers to a detailed and sequential breakdown of the solution or reasoning behind the answer. This comprehensive explanation walks through each step of the answer, offering you clarity and understanding.
Our explanations are based on the best information we have, but they may not always be right or fit every situation.
Our explanations are based on the best information we have, but they may not always be right or fit every situation.
The blue check mark means that this solution has been answered and checked by an expert. This guarantees that the final answer is accurate.
Learn more on how we answer questions.
Learn more on how we answer questions.
Related Answered Questions
Question: 32.7
Verified Answer:
With the full-load output of 500 \mathrm{k...
Question: 32.9
Verified Answer:
(a) Primary phase voltage = 3300/1.73 = ...
Question: 32.6
Verified Answer:
(a) Full-load secondary current is
\frac{50...
Question: 32.5
Verified Answer:
Per-unit resistance drop of a transformer
\...
Question: 32.4
Verified Answer:
(a) From equation [32.9],
R_{\mathrm{e}}=R_...
Question: 32.3
Verified Answer:
If I_{2^{\prime}} represents the co...
Question: 32.2
Verified Answer:
(a) From [32.4]
E_1 = 4.44 N_1 f Φ_m[/latex...