Question 3.17: The maximum flux density in the core of a 1100/220 V, 50 Hz,...

The maximum flux density in the core of a 1100/220 V, 50 Hz, 100 kVA transformer is 3.5 Wb/m². Calculate the area of cross section of the core and the number of turns of the primary and secondary windings if the EMF per turn is 5.5 V.

The blue check mark means that this solution has been answered and checked by an expert. This guarantees that the final answer is accurate.
Learn more on how we answer questions.

V_{1} = E_{1} = 1100  V

EMF per turn × No. of turns = total induced EMF

or,                                                 5.5 × N_{1} = E_{1}

or,                                                 N_{1} = \frac{1100}{5.5}=200 turns.

\frac{E_{1}}{E_{2}}=\frac{V_{1}}{V_{2}}=\frac{N_{1}}{N_{2}}

N_{2}=N_{1} \left(\frac{E_{2}}{E_{1}}\right) =200 \left(\frac{220}{1100}\right) = 50 turns.

Again,                    E_{1} = 4.44  Φ_{m}  f  N_{1}
or,                           E_{1} = 4.44  B_{m}  A  f  N_{1}

A= \frac{E_{1}}{4.44  B_{m}  f  N_{1}}=\frac{1100}{4.44  ×  3.5  ×  50  ×  200}

= 70 × 10^{–4}  m^{2}
= 70  cm^{2}