Question 1.2: The three-winding single-phase transformer of Figure 1.1 is ...
The three-winding single-phase transformer of Figure 1.1 is rated at 13.8 kV/138 kV/4.157 kV and 50 MVA/40 MVA/10 MVA. Terminations are as follows:
13.8 kV winding: 13.8 kV Source
138 kV winding: 35 MVA load, pf = 0.866 lagging
4.157 kV winding: 5 MVA load, pf = 0.866 leading
Using S_{base} = 10 MVA, and voltage ratings as bases,
(a) Draw the pu equivalent circuit.
(b) Solve for the primary current, power, and power, and power factor.