Question 11.4: A Two-Stage Refrigeration Cycle with a Flash Chamber Conside...

A Two-Stage Refrigeration Cycle with a Flash Chamber

Consider a two-stage compression refrigeration system operating between the pressure limits of 0.8 and 0.14 MPa. The working fluid is refrigerant-134a. The refrigerant leaves the condenser as a saturated liquid and is throttled to a flash chamber operating at 0.32 MPa. Part of the refrigerant evaporates during this flashing process, and this vapor is mixed with the refrigerant leaving the low-pressure compressor. The mixture is then compressed to the condenser pressure by the high-pressure compressor. The liquid in the flash chamber is throttled to the evaporator pressure and cools the refrigerated space as it vaporizes in the evaporator. Assuming the refrigerant leaves the evaporator as a saturated vapor and both compressors are isentropic, determine (a) the fraction of the refrigerant that evaporates as it is throttled to the flash chamber, (b) the amount of heat removed from the refrigerated space and the compressor work per unit mass of refrigerant flowing through the condenser, and (c) the coefficient of performance.

The Blue Check Mark means that this solution has been answered and checked by an expert. This guarantees that the final answer is accurate.
Learn more on how we answer questions.

A two-stage compression refrigeration system operating between specified pressure limits is considered. The fraction of the refrigerant that evaporates in the flash chamber, the refrigeration and work input per unit mass, and the COP are to be determined.
Assumptions 1 Steady operating conditions exist. 2 Kinetic and potential energy changes are negligible. 3 The flash chamber is adiabatic.
Properties The enthalpies of the refrigerant at various states are determined from the refrigerant tables and are indicated on the T-s diagram.
Analysis The T-s diagram of the refrigeration cycle is shown in Fig. 11–13. We note that the refrigerant leaves the condenser as saturated liquid and enters the low-pressure compressor as saturated vapor.
(a) The fraction of the refrigerant that evaporates as it is throttled to the flash chamber is simply the quality at state 6, which is

x_{6}=\frac{h_{6}-h_{f}}{h_{f g}}=\frac{95.47-55.16}{196.71}=0.2049

(b) The amount of heat removed from the refrigerated space and the compressor work input per unit mass of refrigerant flowing through the condenser are

\begin{aligned}q_{L} &=\left(1-x_{6}\right)\left(h_{1}-h_{8}\right) \\&=(1-0.2049)[(239.16-55.16) kJ / kg ]=146.3 kJ / kg\end{aligned}

and

w_{\text {in }}=w_{\text {comp I,in }}+w_{\text {comp II,in }}=\left(1-x_{6}\right)\left(h_{2}-h_{1}\right)+(1)\left(h_{4}-h_{9}\right)

The enthalpy at state 9 is determined from an energy balance on the mixing chamber,

\begin{aligned} \dot{E}_{\text {out }} &=\dot{E}_{\text {in }} \\ (1) h_{9} &=x_{6} h_{3}+\left(1-x_{6}\right) h_{2} \\ h_{9} &=(0.2049)(251.88)+(1-0.2049)(255.93)=255.10 kJ / kg \end{aligned}

Also, S_{9}=0.9416 kJ / kg \cdot K . Thus the enthalpy at state 4 (0.8 MPa, S_{4}= s_{9} \text { ) is } h_{4}=274.48 kJ / kg. Substituting,

\begin{aligned} w_{ in } &=(1-0.2049)[(255.93-239.16) kJ / kg ]+(274.48-255.10) kJ / kg \\ &= 3 2 . 7 1 kJ / kg \end{aligned}

(c) The coefficient of performance is

COP _{ R }=\frac{q_{L}}{w_{\text {in }}}=\frac{146.3 kJ / kg }{32.71 kJ / kg }=4.47

Discussion This problem was worked out in Example 11–1 for a single-stage refrigeration system (COP = 3.97) and in Example 11–3 for a two-stage cascade refrigeration system (COP = 4.46). Notice that the COP of the refrigeration system increased considerably relative to the single-stage compression but did not change much relative to the two-stage cascade compression.