Question 10.8: An Ideal Cogeneration Plant Consider the cogeneration plant ...

An Ideal Cogeneration Plant

Consider the cogeneration plant shown in Fig. 10–23. Steam enters the turbine at 7 MPa and 500°C. Some steam is extracted from the turbine at 500 kPa for process heating. The remaining steam continues to expand to 5 kPa. Steam is then condensed at constant pressure and pumped to the boiler pressure of 7 MPa. At times of high demand for process heat, some steam leaving the boiler is throttled to 500 kPa and is routed to the process heater. The extraction fractions are adjusted so that steam leaves the process heater as a saturated liquid at 500 kPa. It is subsequently pumped to 7 MPa. The mass flow rate of steam through the boiler is 15 kg/s. Disregarding any pressure drops and heat losses in the piping and assuming the turbine and the pump to be isentropic, determine (a) the maximum rate at which process heat can be supplied, (b) the power produced and the utilization factor when no process heat is supplied, and (c) the rate of process heat supply when 10 percent of the steam is extracted before it enters the turbine and 70 percent of the steam is extracted from the turbine at 500 kPa for process heating.

The Blue Check Mark means that this solution has been answered and checked by an expert. This guarantees that the final answer is accurate.
Learn more on how we answer questions.

A cogeneration plant is considered. The maximum rate of process heat supply, the power produced and the utilization factor when no process heat is supplied, and the rate of process heat supply when steam is extracted from the steam line and turbine at specified ratios are to be determined.
Assumptions 1 Steady operating conditions exist. 2 Pressure drops and heat losses in piping are negligible. 3 Kinetic and potential energy changes are negligible.

Analysis The schematic of the cogeneration plant and the T-s diagram of the cycle are shown in Fig. 10–23. The power plant operates on an ideal

cycle and thus the pumps and the turbines are isentropic; there are no pressure drops in the boiler, process heater, and condenser; and steam leaves the condenser and the process heater as saturated liquid.
The work inputs to the pumps and the enthalpies at various states are as follows:

\begin{aligned}w_{\text {pump I,in }} &=v_{8}\left(P_{9}-P_{8}\right)=\left(0.001005 m ^{3} / kg \right)[(7000-5) kPa ]\left(\frac{1 kJ }{1 kPa \cdot m ^{3}}\right) \\&=7.03 kJ / kg \\w_{\text {pump II,in }} &=v_{7}\left(P_{10}-P_{7}\right)=\left(0.001093 m ^{3} / kg \right)[(7000-500) kPa ]\left(\frac{1 kJ }{1 kPa \cdot m ^{3}}\right) \\&=7.10 kJ / kg \\h_{1} &=h_{2}=h_{3}=h_{4}=3411.4 kJ / kg \\h_{5} &=2739.3 kJ / kg \\h_{6} &=2073.0 kJ / kg \\h_{7} &=h_{f @ 500 kPa }=640.09 kJ / kg \\h_{8} &=h_{f @ 5 kPa }=137.75 kJ / kg \\h_{9} &=h_{8}+w_{\text {pump } I , \text { in }}=(137.75+7.03) kJ / kg =144.78 kJ / kg \\h_{10} &=h_{7}+w_{\text {pump II,in }}=(640.09+7.10) kJ / kg =647.19 kJ / kg\end{aligned}

(a) The maximum rate of process heat is achieved when all the steam leaving the boiler is throttled and sent to the process heater and none is sent to the turbine \text { (that is, } \dot{m}_{4}=\dot{m}_{7}=\dot{m}_{1}=15 kg / s \text { and } \dot{m}_{3}=\dot{m}_{5}=\dot{m}_{6}=0 \text { ) } . Thus,

\dot{Q}_{p, \max }=\dot{m}_{1}\left(h_{4}-h_{7}\right)=(15 kg / s )[(3411.4-640.09) kJ / kg ]=41,570 kW

The utilization factor is 100 percent in this case since no heat is rejected in the condenser, heat losses from the piping and other components are assumed to be negligible, and combustion losses are not considered.
(b) When no process heat is supplied, all the steam leaving the boiler passes through the turbine and expands to the condenser pressure of 5 kPa (that is, \dot{m}_{3}=\dot{m}_{6}=\dot{m}_{1}=15 kg / s \text { and } \dot{m}_{2}=\dot{m}_{5}=0 ). Maximum power is produced in this mode, which is determined to be

\begin{aligned} \dot{W}_{\text {turb,out }} &=\dot{m}\left(h_{3}-h_{6}\right)=(15 kg / s )[(3411.4-2073.0) kJ / kg ]=20,076 kW \\ \dot{W}_{\text {pump,in }} &=(15 kg / s )(7.03 kJ / kg )=105 kW \\ \dot{W}_{\text {net,out }} &=\dot{W}_{\text {turb,out }}-\dot{W}_{\text {pump,in }}=(20,076-105) kW =19,971 kW \cong 20.0 MW \\ \dot{Q}_{\text {in }} &=\dot{m}_{1}\left(h_{1}-h_{11}\right)=(15 kg / s )[(3411.4-144.78) kJ / kg ]=48,999 kW \end{aligned}

Thus,

\epsilon_{u}=\frac{\dot{W}_{\text {net }}+\dot{Q}_{p}}{\dot{Q}_{\text {in }}}=\frac{(19,971+0) kW }{48,999 kW }=0.408 \text { or } 40.8 \%

That is, 40.8 percent of the energy is utilized for a useful purpose. Notice that the utilization factor is equivalent to the thermal efficiency in this case.
(c) Neglecting any kinetic and potential energy changes, an energy balance on the process heater yields

\begin{aligned} \dot{E}_{\text {in }} &=\dot{E}_{\text {out }} \\ \dot{m}_{4} h_{4}+\dot{m}_{5} h_{5} &=\dot{Q}_{p, \text { out }}+\dot{m}_{7} h_{7} \end{aligned}

or

\dot{Q}_{p,out}= \dot{m}_{4}h_4+\dot{m}_{5}h_5-\dot{m}_{7}h_7

where

\begin{aligned}&\dot{m}_{4}=(0.1)(15 kg / s )=1.5 kg / s \\&\dot{m}_{5}=(0.7)(15 kg / s )=10.5 kg / s \\&\dot{m}_{7}=\dot{m}_{4}+\dot{m}_{5}=1.5+10.5=12 kg / s\end{aligned}

Thus

\begin{aligned}\dot{Q}_{p, \text { out }}=&(1.5 kg / s )(3411.4 kJ / kg )+(10.5 kg / s )(2739.3 kJ / kg ) \\&-(12 kg / s )(640.09 kJ / kg ) \\=& 26.2 MW\end{aligned}

Discussion Note that 26.2 MW of the heat transferred will be utilized in the process heater. We could also show that 11.0 MW of power is produced in this case, and the rate of heat input in the boiler is 43.0 MW. Thus the utilization factor is 86.5 percent.