Question : Chilling of Beef Carcasses in a Meat Plant The chilling room...

Chilling of Beef Carcasses in a Meat Plant

The chilling room of a meat plant is 18  m \times 20  m \times 5.5  m in size and has a capacity of 450 beef carcasses. The power consumed by the fans and the lights of the chilling room are 26 and 3 kW, respectively, and the room gains heat through its envelope at a rate of 13 kW. The average mass of beef carcasses is 285 kg. The carcasses enter the chilling room at 36^{\circ}  C after they are washed to facilitate evaporative cooling and are cooled to 15^{\circ}  C in 10 h. The water is expected to evaporate at a rate of 0.080 kg/s. The air enters the evaporator section of the refrigeration system at 0.7^{\circ}  C and leaves at - 2^{\circ}  C. The air side of the evaporator is heavily finned, and the overall heat transfer coefficient of the evaporator based on the air side is 20  W / m ^{2} \cdot{ }^{\circ} C . Also, the average temperature difference between the air and the refrigerant in the evaporator is 5.5^{\circ} C.Determine (a) the refrigeration load of the chilling room, (b) the volume flow rate of air, and (c) the heat transfer surface area of the evaporator on the air side, assuming all the vapor and the fog in the air freezes in the evaporator.

The Blue Check Mark means that this solution has been answered and checked by an expert. This guarantees that the final answer is accurate.
Learn more on how we answer questions.

SOLUTION  The chilling room of a meat plant with a capacity of 450 beef carcasses is considered. The cooling load, the airflow rate, and the heat transfer area of the evaporator are to be determined.

Assumptions  1 Water evaporates at a rate of 0.080 kg/s. 2 All the moisture in the air freezes in the evaporator.

Properties  The heat of fusion and the heat of vaporization of water at 0^{\circ}  C are 333.7 kJ/kg and 2501 kJ/kg (Table A-9). The density and specific heat of air at 0^{\circ}  C are 1.292  kg / m ^{3} \text { and } 1.006  kJ / kg \cdot{ }^{\circ} C (Table A-15). Also, the specific heat of beef carcass is determined from the relation in Table A-7b to be

C_{p} = 1.68 + 2.51 \times(\text { water content })

 

             = 1.68+2.51 \times 0.58 = 3.14  kJ / kg \cdot{ }^{\circ} C

 

Analysis  (a) A sketch of the chilling room is given in Figure. The amount of beef mass that needs to be cooled per unit time is

m_{\text {beef }}=(\text { Total beef mass cooled }) /(\text { Cooling time })

 

= (450 \text {carcasses })(285  kg / \text {carcass}) /(10 \times 3600  s )= 3.56  kg / s

 

The product refrigeration load can be viewed as the energy that needs to be removed from the beef carcass as it is cooled from 36 to 15^{\circ}  C at a rate of 3.56 kg/s and is determined to be Then the total refrigeration load of the chilling room becomes

\dot{Q}_{\text {total chillroom }}=\dot{Q}_{\text {beef }}+\dot{Q}_{\text {fan }}+\dot{Q}_{\text {lights }}+\dot{Q}_{\text {heat gain }}

 

                                         = 235 + 26 + 3 + 13 = 277  kW

 

The amount of carcass cooling due to evaporative cooling of water is

\dot{Q}_{\text {beef, evaporative }} = \left(m h_{f g}\right)_{\text {water }}

 

                 =(0.080  kg / s )(2490  kJ / kg ) = 199  kW

 

which is 199/235 = 85 percent of the total product cooling load. The remaining 15 percent of the heat is transferred by convection and radiation.

 

(b) Heat is transferred to air at the rate determined above, and the temperature of the air rises from -2^{\circ}  C \text { to } 0.7^{\circ}  C as a result. Therefore, the mass flow rate of air is

\dot{m}_{\text {air }}=\frac{\dot{Q}_{\text {air }}}{\left(C_{p} \Delta T_{\text {air }}\right)}=\frac{277 kW }{\left(1.006  kJ / kg \cdot{ }^{\circ} C \right)\left[0.7-(-2){ }^{\circ} C \right]} = 102.0  kg / s

 

Then the volume flow rate of air becomes

\dot{V}_{\text {air }}=\frac{\dot{m}_{\text {air }}}{\rho_{\text {air }}} = \frac{102  kg / s }{1.292  kg / m ^{3}} = 78.9  m ^{3} / s

 

(c) Normally the heat transfer load of the evaporator is the same as the refrigeration load. But in this case the water that enters the evaporator as a liquid is frozen as the temperature drops to -2^{\circ}  C , and the evaporator must also remove the latent heat of freezing, which is determined from

\dot{Q}_{\text {freezing }}=\left(\dot{m} h_{\text {latent }}\right)_{\text {water }}

 

                                   = (0.080  kg / s )(334  kJ / kg ) = 27  kW

 

Therefore, the total rate of heat removal at the evaporator is

\dot{Q}_{\text {evaporator }}=\dot{Q}_{\text {total, chill room }}+\dot{Q}_{\text {freezing }}=277+27 = 304  kW

 

Then the heat transfer surface area of the evaporator on the air side is determined from \dot{Q}_{\text {evaporator }}=(U A)_{\text {airside }} \Delta T,

 

A=\frac{\dot{Q}_{\text {evaporator }}}{U \Delta T}=\frac{304,000  W }{\left(20  W / m ^{2} \cdot{ }^{\circ} C \right)\left(5.5^{\circ}  C \right)} = 2764  m ^{2}

 

Obviously, a finned surface must be used to provide such a large surface area on the air side.

138