Consider proportional-only control of the level control system in Fig. 11.16. The level transmitter has a span of 10 ft. and a zero of 15 ft. Recall that the standard instrument ranges are 4 to 20 mA and 3 to 15 psia. The nominal design conditions are h=20 ft. The controller has a gain of 5 while the gain for the control valve is K_{v}=0.4 cfm / psi, respectively. The time constant for the tank is \tau=5 min. After the set-point is changed from 20 to 22 ft, the tank level eventually reaches a new steady-state value of 21.92 ft.
(a) What is the offset?
(b) What are the gains K_{m} and K_{p} in Fig. 11.16? (Give their units also)
(c) How could the controller be modified to obtain zero offset?