Question 10.2: Determine the reduction in the annual energy costs due to st...

Determine the reduction in the annual energy costs due to staggered duty cycling of three identical fan motors (each rated at 30 kW [40 hp]). The motor manufacturer specifies 20 minutes on and 10 minutes off as the minimum duty cycle. The utility monthly demand charge is $10/kW. First, determine the recommended NEMA duty period assuming 2-pole motors.

The Blue Check Mark means that this solution has been answered and checked by an expert. This guarantees that the final answer is accurate.
Learn more on how we answer questions.

(a) Using Table 10.2, the allowable number of starts per hour for 40 hp, 2-pole motors is 3.7 starts/hr. Thus each start should last:

Start period = (60 min/hr)/(3.7 starts/hr) = 14.4 min/start

The duty period is thus about 15 minutes. Because the duty period is the sum of off-time and on-time, and because the minimum off-time is about 2 minutes (130 seconds based on Table 10.2), the maximum on-time allowable by the NEMA standard is 13 minutes. Thus, the manufacturer on-time is longer than that recommended by NEMA.

(b) The reduction in the electrical demand peak due to the staggered duty cycling approach is 1/3 of the total demand of all three motors (or 1/3 * 90 kW = 30 kW). Indeed, at any given time, only two out of the three motors are operating. Thus, the annual savings in electrical demands charges is given as follows:

ΔkW =12*30kW = 360kW/yr

Therefore, the staggered duty cycling control provides an annual energy cost savings of $3,600.

Table 10.2 Summary of Comparative Results for the Control and Measurement Techniques Tested by Krarti et al. (2000).

Outside Air Intake Rate Measurements
Electronic Thermal Anemometry Averaging Pitot-Tube Array
RMS (cfm) stdev (cfm) Mean (cfm) RMS (cfm) ev (cfm) Mean (cfm) Validity Set-Point
(cfm)
Case Measurement
Control1
System Description
1048 564 682 1,150 658 656 14% 1,600 1A NA Fixed Damper Position
1,199 680 1,407 1,199 678 1,410 23% 2,400 1B NA Fixed Damper Position
1,513 870 2,124 1,309 819 2,178 26% 3,200 1C NA Fixed Damper Position
89 70 1,544 75 69 1,630 100% 1,600 2A NA Plenum Pressure Control
118 88 3,279 129 94 3,288 100% 3,200 2C NA Plenum Pressure Control
71 46 1,546 52 38 1,635 100% 1,600 3A P Direct Control with
Economizer Duct
53 47 3,225 51 50 3,192 100% 3,200 3C P Direct Control with
Economizer Duct
67 55 1,637 110 55 1,695 94% 1,600 4A E Direct Control with
Economizer Duct
80 50 3,263 57 49 3,228 100% 3,200 4C E Direct Control with
Economizer Duct
953 458 2,436 936 439 2,427 0% 1,600 5A E Volume Tracking
58 47 1,634 55 39 1,639 100% 1,600 6A P Direct Control with
Dedicated Duct
77 51 2,457 51 41 2,430 100% 2,400 6B P Direct Control with
Dedicated Duct
58 43 1,640 56 36 1,643 100% 1,600 7A E Direct Control with
Dedicated Duct
50 42 2,428 40 39 2,404 100% 2,400 7B E Direct Control with
Dedicated Duct
42 36 1,622 37 31 1,621 100% 1,600 8A P Injection Fan
54 36 2,440 40 28 2,429 100% 2,400 8B P Injection Fan
40 36 1,617 44 38 1,622 100% 1,600 9A E Injection Fan
42 32 2,427 37 33 2,418 100% 2,400 9B E Injection Fan
119^{3} 119^{3} 1,605^{3} 141 137 1,632 75% 1,600 NA^{2} C Direct Control

1: P = Averaging Pitot-Tube Array, E = Electronic Thermal Anemometer, C = CO_{2} Concentration Balance.
2: A different system setup was used for testing the concentration balance measurement technique.
3: Value is for CO_{2} concentration balance measurement technique, not electronic thermal anemometry.

Related Answered Questions