Fire Spinkler
The specification for a certain residential fire-suppression system is that water should be sprayed at the rate q of 10 gal/min. For the revision of a technical manual intended for customers outside the United States, express the flow rate in the SI based on a time interval of 1 s.
Approach
To complete this problem, we need to apply conversion factors for both volume and time. Referring to Table 3.6
Table 3.6 Conversion Factors between Certain Quantities in the USCS and SI
Quantity | Conversion |
Length | 1 in. = 25.4 mm |
1 in. = 0.0254 m | |
1 ft = 0.3048 m | |
1 mi = 1.609 km | |
1 mm = 3.9370 ×10^{-2} in. | |
1 m = 39.37 in. | |
1 m = 3.2808 ft | |
1 km = 0.6214 mi | |
Area | 1 in^2 = 645.16 mm^2 |
1 ft^2 = 9.2903 × 10^{-2} m^2 | |
1 mm^2 = 1.5500 × 10^{-3 }in^2 | |
1 m^2 = 10.7639 ft^2 | |
Volume | 1 ft^3 = 2.832 × 10^{-2} m^3 |
1 ft^3 = 28.32 L | |
1 gal = 3.7854 × 10^{-3} m^3 | |
1 gal = 3.7854 L | |
1 m^3 = 35.32 ft^3 | |
1 L = 3.532 × 10^{-2} ft^3 | |
1 m^3 = 264.2 gal | |
1 L = 0.2642 gal | |
Mass | 1 slug = 14.5939 kg |
1 lbm = 0.45359 kg | |
1 kg = 6.8522 × 10^{-2} slugs | |
1 kg = 2.2046 lbm | |
Force | 1 lb = 4.4482 N |
1 N = 0.22481 lb | |
Pressure or stress | 1 psi = 6895 Pa |
1 psi = 6.895 kPa | |
1 Pa = 1.450 × 10^{-4 }psi | |
1 kPa = 0.1450 psi | |
Work, energy, or heat | 1 ft · lb = 1.356 J |
1 Btu = 1055 J | |
1 J = 0.7376 ft · lb | |
1 J = 9.478 × 10^{-4} Btu | |
Power | 1 (ft · lb)/s = 1.356 W |
1 hp = 0.7457 kW | |
1 W = 0.7376 (ft · lb)/s | |
1 kW = 1.341 hp |
we could express volume in the SI using the dimensions of either m^{3} or L. We assume that a cubic meter is much larger than the amount of water we expect to be sprayed each second; so we initially decide to convert volume to liters with the conversion factor 1 gal = 3.785 L. We will double-check that assumption after we complete the calculation.