The open-circuit test data of a 500 kVA , 4000 volt, 8 pole, 3 -phase, 50 Hz alternator is:
ATs, per pole 2000 3000 3560 5000 6200 7000 8000
Terminal voltage 1990 2900 3400 4000 4400 45900 4800
The equivalent armature reaction expressed in ampere-turn per pole is 1.1 \times ampere conductors per pole per phase. There are 240 conductors per phase in series. If the inductive voltage drop 8 \% on full load and the resistance drop is negligible. Then determine (i) Short circuit characteristic (ii) field excitation and regulation for full load at 0-8 p . f . lagging.