Question 11.5: The Simple Ideal Gas Refrigeration Cycle An ideal gas refrig...

The Simple Ideal Gas Refrigeration Cycle

An ideal gas refrigeration cycle using air as the working medium is to maintain a refrigerated space at 0°F while rejecting heat to the surrounding medium at 80°F. The pressure ratio of the compressor is 4. Determine (a) the maximum and minimum temperatures in the cycle, (b) the coefficient of performance, and (c) the rate of refrigeration for a mass flow rate of 0.1 lbm/s.

The Blue Check Mark means that this solution has been answered and checked by an expert. This guarantees that the final answer is accurate.
Learn more on how we answer questions.

An ideal gas refrigeration cycle using air as the working fluid is considered. The maximum and minimum temperatures, the COP, and the rate of refrigeration are to be determined.
Assumptions 1 Steady operating conditions exist. 2 Air is an ideal gas with variable specific heats. 3 Kinetic and potential energy changes are negligible.
Analysis The T-s diagram of the gas refrigeration cycle is shown in Fig. 11–20. We note that this is an ideal gas-compression refrigeration cycle, and thus, both the compressor and the turbine are isentropic, and the air is cooled to the environment temperature before it enters the turbine.

(a) The maximum and minimum temperatures in the cycle are determined from the isentropic relations of ideal gases for the compression and expansion processes. From Table A–17E,

\begin{gathered}T_{1}=460 R \longrightarrow h_{1}=109.90 Btu / lbm \text{ and } P_{r 1}=0.7913\end{gathered}

P_{r 2}=\frac{P_{2}}{P_{1}} P_{r 1}=(4)(0.7913)=3.165\longrightarrow \begin{cases} h_{2}=163.5 \text{ Btu/lbm} \\T_{2}=683 R \left(\text { or } 223^{\circ} F \right)\end{cases} \\[0.5cm] T_{3}=540 R\longrightarrow h_3 =129.06 \text{ Btu/lbm and }P_{r 3}=1.3860\\[0.5cm] P_{r 4}=\frac{P_{4}}{P_{3}} P_{r 3}=(0.25)(1.386)=0.3465\longrightarrow \begin{cases} h_{4}=86.7 \text{ Btu/lbm } \\T_{4}=363 R \left(\text { or }-97^{\circ} F \right) \end{cases}

Therefore, the highest and the lowest temperatures in the cycle are 223 and -97°F, respectively.

(b) The COP of this ideal gas refrigeration cycle is

COP _{ R }=\frac{q_{L}}{w_{\text {net, in }}}=\frac{q_{L}}{w_{\text {comp,in }}-W_{\text {turb,out }}}

where

\begin{aligned}q_{L} &=h_{1}-h_{4}=109.9-86.7=23.2 Btu / lbm \\W_{\text {turb,out }} &=h_{3}-h_{4}=129.06-86.7=42.36 Btu / lbm \\W_{\text {comp,in }} &=h_{2}-h_{1}=163.5-109.9=53.6 Btu / lbm\end{aligned}

Thus,

COP _{ R }=\frac{23.2}{53.6-42.36}=2.06

(c) The rate of refrigeration is

\dot{Q}_{\text {refrig }}=\dot{m}\left(q_{L}\right)=(0.1 lbm / s )(23.2 Btu / lbm )=2.32 Btu / s

Discussion It is worth noting that an ideal vapor-compression cycle working under similar conditions would have a COP greater than 3.

11-20