Question 3.20: Three 1-phase 20-kVA, 2000/200-V transformers identical with...

Three 1-phase 20-kVA, 2000/200-V transformers identical with that of Ex. 3.3 are connected in Y/ \Delta  in a 3-phase, 60 kVA bank to step-down the voltage at the load end of a feeder having impedance of 0.13 + j 0.95 \Omega /phase. The line voltage at the sending-end of the feeder is 3464 V. The transformers supply a balanced 3-phase load through a feeder whose impedance is 0.0004 + j 0.0015 \Omega/phase. Find the load voltage (line-to-line) when it draws rated current from transformers at 0.8 lagging power factor.

The Blue Check Mark means that this solution has been answered and checked by an expert. This guarantees that the final answer is accurate.
Learn more on how we answer questions.

Figure 3.58 gives the circuit diagram of the system. The computations will be carried out on per phase-Y basis by referring all quantities to the HV (Y-connected) side of the transformer bank.

LV feeder impedance referred to the HV side is

  1. \left(\frac{2000\sqrt{3} }{200} \right) ^{2} (0.0004+j0.0015) =0.12+ j0.45 \Omega /phase

The total series impedance of the HV and LV feeders referred to the HV side is

Z_{F}=(0.13+j0.95) +(0.12+ j0.45)

 

= 0.25 + j 1.4 \Omega /phase

From Ex. 3.5, the equivalent impedance of the transformer bank is referred to the HV side

Z_{T}= 0.82 + j 1.02 \Omega /phase Y

Sending-end feeder voltage =\frac{3464}{\sqrt{3} } =2000V/phase Y

Load current on the HV side = rated current of transformer

= 10 A/phase Y

It is now seen that the equivalent circuit for one phase referred to the Y-connected HV side is exactly the same as in Ex. 3.6, Fig. 3.20. Thus the load voltage referred to the HV side is 197.692 V to neutral. The actual load voltage is 197.688 V, line-to-line (since the secondaries are \Delta -connected).

PU method In such problems it is convenient to use the pu method. We shall choose the following base values:

(MVA)_{B}=\frac{3\times 20}{1000} =0.06

Voltage base on HV side =2\sqrt{3} kV (line-to-line)

Voltage base on LV side =0.2 kV (line-to-line)

Note The voltage base values are in the ratio of line-to-line voltages (same as phase voltages on equivalent star basis)

\bar{Z}_{1} (LV  line)(pu) = (0.0004 + j 0.0015)\times \frac{0.06}{(0.2)^{2}} = (0.06 + j 0.225)\times 10^{-2}

 

\bar{Z}_{2} (HV  line)(pu) = (0.13 + j 0.95)\times \frac{0.06} {(2\sqrt{3}) ^{2}} = (0.065 + j 0.475)\times 10^{-2}

 

\bar{Z}_{T} (star  side)(pu) = (0.82 + j 1.02)\times \frac{0.06}{(2\sqrt{3} )^{2}} = (0.41 + j 0.51)\times 10^{-2}

Note Suppose the transformer impedance was given on the delta side

\bar{Z}_{T} (delta  side)(pu) = \left(\frac{200}{2000} \right)^{2} \times (0.82+ j1.02) (0.82 + j 1.02) \times 10^{–2} \Omega (delta phase)

Equivalent star impedance =\frac{1}{3} (0.82 + j 1.02) \times 10^{-2}\Omega

\bar{Z}_{T} (pu) = \frac{0.06}{(0.2)^{2}} \times \frac{1}{3} (0.82 + j 1.02)\times 10^{–2}

= (0.41 + j 0.51)\times 10^{–3} (same as calculated above)

\bar{Z}(total) (pu) = 0.06 + j 0.225

0.065 + j 0.475

0.41 + j 0.51

(0.535 +j1.21) \times 10^{2}

 

V_{1}(sending–end  voltage)= 2\sqrt{3} kV (line) or 1 pu [/latex]

 

I_{1} (= rated  current)= 1 pu;  pf= 0.8 lag

 

V_{1}(load  voltage) = 1 – 1 (0.535 \times 0.8 + 1.2 \times 0.6)\times 10^{–2}

 

= 0.98846  pu

 

= 0.98846 \times 200 = 197.692 V  (line)
3 20

Related Answered Questions