Question 5.1: A kerosene stream with a flow rate of 45,000 lb/h is to be c...

A kerosene stream with a flow rate of 45,000 lb/h is to be cooled from 390 ºF to 250 ºF by heat exchange with 150,000 lb/h of crude oil at 100 ºF. A maximum pressure drop of 15 psi has been specified for each stream. Prior experience with this particular oil indicates that it exhibits significant fouling tendencies, and a fouling factor of 0.003 h · ft² · ºF/Btu is recommended. Physical properties of the two streams are given in the table below. Design a shell-and-tube heat exchanger for this service.

Fluid Property Kerosene Crude Oil
C_{P} (Btu/lbm·ºF) 0.59 0.49
k (Btu/h · ft · ºF) 0.079 0.077
μ (lbm/ft · h) 0.97 8.7
Specific gravity 0.785 0.85
Pr 7.24 55.36
The blue check mark means that this solution has been answered and checked by an expert. This guarantees that the final answer is accurate.
Learn more on how we answer questions.

(a) Make initial specifications.
(i) Fluid placement
Kerosene is not corrosive, but crude oil may be, depending on salt and sulfur contents and temperature. At the low temperature of the oil stream in this application, however, corrosion should not be a problem provided the oil has been desalted (if necessary). Nevertheless, the crude oil should be placed in the tubes due to its relatively high fouling tendency. Also, the kerosene should be placed in the shell due to its large ΔT of 140ºF according to the guidelines given in Table 3.4.

TABLE 3.4 Criteria for Fluid Placement, in Order of Priority

Tube-Side Fluid Shell-Side Fluid
Corrosive fluid Condensing vapor (unless corrosive)
Cooling water Fluid with large ΔT (>100ºF)
Fouling fluid
Less viscous fluid
Higher-pressure stream
Hotter fluid

(ii) Shell and head types
The recommended fouling factor for kerosene is 0.001–0.003 h · ft² · ºF/Btu (Table 3.3), indicating a significant fouling potential. Therefore, a floating-head exchanger is selected to permit mechanical cleaning of the exterior tube surfaces. Also, the floating tubesheet will allow for differential thermal expansion due to the large temperature difference between the two streams. Hence, a type AES exchanger is specified.

TABLE 3.3 Typical Values of Fouling Factors (h . ft² . ºF/Btu)dcont’d

Cooling water streams^a
\bullet  Seawater 0.0005–0.001
\bullet  Brackish water 0.001–0.002
\bullet  Treated cooling tower water 0.001–0.002
\bullet  Municipal water supply 0.001–0.002
\bullet  River water 0.001–0.003
\bullet  Engine jacket water 0.001
\bullet  Distilled or demineralized water 0.0005
\bullet  Treated boiler feedwater 0.0005–0.001
\bullet  Boiler blowdown 0.002
Service gas streams
\bullet  Ambient air (in air-cooled units) 0–0.0005
\bullet  Compressed air 0.001–0.002
\bullet  Steam (clean) 0–0.0005
\bullet  Steam (with oil traces) 0.001–0.002
\bullet  Refrigerants (with oil traces) 0.002
\bullet  Ammonia 0.001
\bullet  Carbon dioxide 0.002
\bullet  Flue gases 0.005–0.01
Service liquid streams
\bullet  Fuel oil 0.002–0.005
\bullet  Lubrication oil 0.001
\bullet  Transformer oil 0.001
\bullet  Hydraulic fluid 0.001
\bullet  Organic heat-transfer fluids 0.001–0.002
\bullet  Refrigerants 0.001
\bullet  Brine 0.003
Process gas streams
\bullet  Hydrogen 0.001
\bullet  Organic solvent vapors 0.001
\bullet  Acid gases 0.002–0.003
\bullet  Stable distillation overhead products 0.001
Process liquid streams
\bullet  Amine solutions 0.002
\bullet  Glycol solutions 0.002
\bullet  Caustic solutions 0.002
\bullet  Alcohol solutions 0.002
\bullet  Ammonia 0.001
\bullet  Vegetable oils 0.003
\bullet  Stable distillation side-draw and bottom products 0.001–0.002
Natural gas processing streams
\bullet  Natural gas 0.001
\bullet  Overhead vapor products 0.001–0.002
\bullet C_3 or C_4 vapor (condensing) 0.001
\bullet  Lean oil 0.002
\bullet  Rich oil 0.001
\bullet  LNG and LPG 0.001
Oil refinery streams
\bullet  Crude oil^b
–   Temperature less than 250ºF 0.002–0.003
–   Temperature between 250ºF and 350ºF 0.003–0.004
–   Temperature between 350ºF and 450ºF 0.004–0.005
–   Temperature greater than 450ºF 0.005–0.006
\bullet  Liquid product streams
–   Gasoline 0.001–0.002
–   Naphtha and light distillates 0.001–0.003
–   Kerosene 0.001–0.003
–   Light gas oil 0.002–0.003
–   Heavy gas oil 0.003–0.005
–   Heavy fuel oils 0.003–0.007
–   Asphalt and residuum 0.007–0.01
\bullet  Other oil streams
–  Refined lube oil 0.001
–  Cycle oil 0.002–0.004
–  Coker gas oil 0.003–0.005
–  Absorption oils 0.0

^aAssumes water velocity greater than 3 ft/s. Lower values of ranges correspond to water temperature below about 120ºF and hot stream temperature below about 250ºF.
^bAssumes desalting at approximately 250ºF and a minimum oil velocity of 2 ft/s.

(iii) Tubing
Following the design guidelines for a fouling oil service, 1 in., 14 BWG tubes are selected with a length of 20 ft.
(iv) Tube layout
Since cleaning of the tube exterior surfaces will be required, square pitch is specified to provide cleaning lanes through the tube bundle. Following the design guidelines, for 1-in. tubes a tube pitch of 1.25 in. is specified.
(v) Baffles
Segmental baffles with a 20% cut are required by the Simplified Delaware method, but this is a reasonable starting point in any case. In consideration of Figure 5.3, a baffle spacing of 0.3 shell diameters is chosen, i.e., B/d_{s} = 0.3.

(vi) Sealing strips
One pair of sealing strips per ten tube rows is specified in accordance with the requirements of the Simplified Delaware method and the design guidelines.
(vii) Construction materials
Since neither fluid is corrosive, plain carbon steel is specified for tubes, shell, and other components.

(b) Energy balances

q=\left(\dot{m} C_{P} \Delta T\right)_{\text {ker }}=45,000 \times 0.59 \times 140=3,717,000  Btu / h

 

3,717,000=\left(\dot{m} C_{p} \Delta T\right)_{\text {oil }}=150,000 \times 0.49 \times \Delta T_{\text {oil }}

 

\Delta T_{\text {oil }}=50.6^{\circ} F

outlet oil temperature = 150.6º F

(c) LMTD.

\left(\Delta T_{\ln }\right)_{c f}=\frac{239.4-150}{\ln (239.4 / 150)}=191.2^{\circ} F

(d) LMTD correction factor.

R=\frac{T_{a}-T_{b}}{t_{b}-t_{a}}=\frac{390-250}{150.6-100}=2.77

 

P=\frac{t_{b}-t_{a}}{T_{a}-t_{a}}=-\frac{150.6-100}{390-100}=0.174

From Figure 3.14 or Equation (3.15), for a 1-2 exchanger F ≅ 0.97. Therefore, one shell pass is required.

F=\frac{\sqrt{R^2+1}\ln\left(\frac{1-S}{1-RS} \right) }{(R-1)\ln\left[\frac{2-S\left(R+1-\sqrt{R^2+1}\right)}{2-S\left(R+1-\sqrt{R^2+1}\right)} \right] }             (3.15)

(e) Estimate U_{D} .
In order to obtain an initial estimate for the size of the exchanger, an approximate value for the overall heat-transfer coefficient is used. From Table 3.5, for a kerosene/oil exchanger, it is found that 20 ≤ U_{D} ≤ 35 Btu/h . ft² . ºF. A value near the middle of the range is selected: U_{D} = 25 Btu/h . ft² . ºF

TABLE 3.5 Typical Values of Overall Heat-Transfer Coefficients in Tubular Heat Exchangers. U = Btu/h . ft² . ºF.

Shell Side Tube Side Design U Includes Total Dirt
Liquid–liquid media
Aroclor 1248 Jet fuels 100–150 0.0015
Cutback asphalt Water 10–20 0.01
Demineralized water Water 300–500 0.001
Ethanol amine (MEA or Water or DEA, or 140–200 0.003
DEA) 10–25% solutions MEA solutions
Fuel oil Water 15–25 0.007
Fuel oil Oil 10–15 0.008
Gasoline Water 60–100 0.003
Heavy oils Heavy oils 10–40 0.004
Heavy oils Water 15–50 0.005
Hydrogen-rich reformer stream Hydrogen-rich reformer stream 90–120 0.002
Kerosene or gas oil Water 25–50 0.005
Kerosene or gas oil Oil 20–35 0.005
Kerosene or jet fuels Trichloroethylene 40–50 0.0015
Jacket water Water 230–300 0.002
Lube oil (low viscosity) Water 25–50 0.002
Lube oil (high viscosity) Water 40–80 0.003
Lube oil Oil 11–20 0.006
Naphtha Water 50–70 0.005
Naphtha Oil 25–35 0.005
Organic solvents Water 50–150 0.003
Organic solvents Brine 35–90 0.003
Organic solvents Organic solvents 20–60 0.002
Tall oil derivatives, vegetable oil, etc. Water 20–50 0.004
Water Caustic soda solutions (10–30%) 100–250 0.003
Water Water 200–250 0.003
Wax distillate Water 15–25 0.005
Wax distillate Oil 13–23 0.005
Condensing vapor-liquid media
Alcohol vapor Water 100–200 0.002
Asphalt (450ºF) Dowtherm vapor 40–60 0.006
Dowtherm vapor Tall oil and derivatives 60–80 0.004
Dowtherm vapor Dowtherm liquid 80–120 0.0015
Gas-plant tar Steam 40–50 0.0055
High-boiling hydrocarbons V Water 20–50 0.003
Low-boiling hydrocarbons A Water 80–200 0.003
Hydrocarbon vapors (partial condenser) Oil 25–40 0.004
Organic solvents A Water 100–200 0.003
Organic solvents high NC, A Water or brine 20–60 0.003
Organic solvents low NC, V Water or brine 50–120 0.003
Kerosene Water 30–65 0.004
Kerosene Oil 20–30 0.005
Naphtha Water 50–75 0.005
Naphtha Oil 20–30 0.005
Stabilizer reflux vapors Water 80–120 0.003
Steam Feed water 400–1000 0.0005
Steam No. 6 fuel oil 15–25 0.0055
Steam No. 2 fuel oil 60–90 0.0025
Sulfur dioxide Water 150–200 0.003
Tall-oil derivatives, vegetable oils (vapor) Water 20–50 0.004
Water Aromatic vapor-stream 40–80 0.005
azeotrope
Gas-liquid media
Air, N_2, etc. (compressed) Water or brine 40–80 0.005
Air, N_2, etc., A Water or brine 10–50 0.005
Water or brine Air, N_2 (compressed) 20–40 0.005
Water or brine Air, N_2, etc., A 5–20 0.005
Water Hydrogen containing natural–gas mixtures 80–125 0.003
Vaporizers
Anhydrous ammonia Steam condensing 150–300 0.0015
Chlorine Steam condensing 150–300 0.0015
Chlorine Light heat-transfer oil 40–60 0.0015
Propane, butane, etc. Steam condensing 200–300 0.0015
Water Steam condensing 250–400 0.0015

NC: non-condensable gas present; V: vacuum; A: atmospheric pressure.
Dirt (or fouling factor) units are (h) (ft²) (ºF)/Btu

(f) Calculate heat-transfer area and number of tubes.

A=\frac{q}{U_{D} F\left(\Delta T_{ ln }\right)_{c f}}=\frac{3,717,000}{25 \times 0.97 \times 191.2}

 

A=801.7  ft ^{2}

 

n_{t}=\frac{A}{\pi D_{0} L}=\frac{801.7}{\pi \times(1 / 12) \times 20}

 

n_{ t }=153

(g) Number of tube passes.
The number of tube passes is chosen to give fully developed turbulent flow in the tubes and a reasonable fluid velocity

R e=\frac{4 \dot{m}\left(n_{p} / n_{ f }\right)}{\pi D_{i} \mu}

 

D_{i}=0.834 \text { in. }=0.0695  ft  (Table B.1)

R e=\frac{4 \times 150,000\left(n_{p} / 153\right)}{\pi \times 0.0695 \times 8.7}=2064.5  n_{p}

We want Re 104 and an even number of passes. Therefore, take n_{p} = 6. Checking the fluid velocity,

V=\frac{\dot{m}\left(n_{p} / n_{t}\right)}{\rho \pi D_{i}^{2} / 4}=\frac{(150,000 / 3600)(6 / 153)}{0.85 \times 62.43 \pi(0.0695)^{2} / 4}=8.1  ft / s

The velocity is at the high end of the recommended range, but still acceptable. Therefore, six tube passes will be used.
(h) Determine shell size and actual tube count.
From the tube-count table for l in. tubes on 1 ¼ -in. square pitch (Table C.5), with six tube passes and a type S head, the listing closest to 153 is 156 tubes in a 21 ¼ -in. shell. Hence, the number of tubes is adjusted to n_{t} = 156 and the shell ID is taken as d_{s} = 21.25 in.
This completes the initial design of the heat exchanger. The initial design must now be rated to determine whether it is adequate for the service. Since the temperature dependence of the fluid properties is not available, they will be assumed constant; the viscosity correction factors will be set to unity and the tube wall temperature will not be calculated.

(i) Calculate the required overall coefficient.

U_{\text {req }}=\frac{q}{n_{ t } \pi D_{o} L F\left(\Delta T_{\ln }\right)_{c f}}=\frac{3,717,000}{156 \times \pi \times(1.0 / 12) \times 20 \times 0.97 \times 191.2}

 

U_{\text {req }}=24.5   Btu / h \cdot ft ^{2} \cdot{ }^{\circ} F

(j) Calculate h_{i}.

R e=\frac{4 \dot{m}\left(n_{p} / n_{t}\right)}{\pi D_{i} \mu}=\frac{4 \times 150,000(6 / 156)}{\pi \times 0.0695 \times 8.7}=12,149

 

h_{i}=\left(k / D_{i}\right) \times 0.023 R e^{0.8} \operatorname{Pr}^{1 / 3}\left(\mu / \mu_{w}\right)^{0.14}

 

=(0.077 / 0.0695) \times 0.023(12,149)^{0.8}(55.36)^{1 / 3}(1.0)

 

h_{i}=180  Btu / h  \cdot ft ^{2} \cdot{ }^{\circ} F

(k) Calculate h_{0}.

B=0.3  d_{s}=0.3 \times 21.25=6.375 in

 

a_{s}=\frac{d_{s} C^{\prime} B}{144 P_{T}}=\frac{21.25 \times 0.25 \times 6.375}{144 \times 1.25}=0.188  ft ^{2}

 

G=\dot{m} / a_{5}=45,000 / 0.188=239,362  lbm / h \cdot ft ^{2}

 

D_{e}=0.99 / 12=0.0825  ft  (from Figure 3.17)

R e=D_{e} G / \mu=0.0825 \times 239,362 / 0.97=20,358

Equation (3.21) is used to calculate the Colburn factor, j_{H}.

j_{H}=0.5\left(1+B / d_{s}\right)\left(0.08 R e^{0.6821}+0.7 R e^{0.1772}\right)

 

=0.5(1+0.3)\left[0.08(20,358)^{0.6821}+0.7(20,358)^{0.1772}\right]

 

j_H=47.8

 

h_{o}=j_{H}\left(k / D_{e}\right) Pr^{1 / 3}\left(\mu / \mu_{w}\right)^{0.14}

 

=47.8(0.079 / 0.0825)(7.24)^{1 / 3}(1.0)

 

h_{o}=88.5  Btu / h \cdot ft ^{2} \cdot{ }^{\circ} F

(1) Calculate the clean overall coefficient.

U_{C}=\left[\frac{D_{o}}{h_{i} D_{i}}+\frac{D_{o} \ln \left(D_{o} / D_{i}\right)}{2 k_{\text {abe }}}+\frac{1}{h_{o}}\right]^{-1}

 

=\left[\frac{1.0}{180 \times 0.834}+\frac{(1.0 / 12) \ln (1.0 / 0.834)}{2 \times 26}+\frac{1}{88.5}\right]^{-1}

 

U_{C}=54.8  Btu / h \cdot ft ^{2} \cdot{ }^{\circ} F

Since U_{C} > U_{req}, continue.
(m) Fouling factors
The fouling factor for the crude oil is specified as 0.003 h . ft² . ºF/Btu, and from Table 3.3, a value of 0.002 h . ft² . ºF/Btu is taken for kerosene. Hence, the total fouling allowance is:

R_{D}=\frac{R_{D i} D_{o}}{D_{i}}+R_{D o}=\frac{0.003 \times 1.0}{0.834}+0.002=0.0056  h \cdot ft ^{2} \cdot{ }^{\circ} F / Btu

 

U_{D}=\left(1 / U_{C}+R_{D}\right)^{-1}=(1 / 54.8+0.0056)^{-1}=41.9  Btu / h \cdot ft ^{2} \cdot{ }^{\circ} F

(n) Calculate the design overall coefficient.

Since U_{D} is much greater than U_{req}, the exchanger is thermally workable, but over-sized.

(o) Over-surface and over-design
It is convenient to perform the calculations using overall coefficients rather than surface areas. The appropriate relationships are as follows

over-surface = U_{C} / U_{r e q}-1=54.8 / 24.5-1=124 \%

over-design = U_{D} / U_{\text {req }}-1=41.9 / 24.5-1=71 \%

Clearly, the exchanger is much larger than necessary.
(p) Tube-side pressure drop
The friction factor is computed using Equation (5.2).

f=0.4137 R e^{-0.2585}=0.4137(12,149)^{-0.2585}=0.03638

 

G=\frac{\dot{m}\left(n_{p} / n_{t}\right)}{\pi D_{i}^{2} / 4}=\frac{150,000(6 / 156)}{\left[\pi(0.0695)^{2} / 4\right]}=1,520,752  lbm / h \cdot ft ^{2}

The friction loss is given by Equation (5.1):

\Delta P_{f}=\frac{f  n_{p} L G^{2}}{7.50 \times 10^{12} D_{i} s \phi}=\frac{0.03638 \times 6 \times 20(1,520,752)^{2}}{7.50 \times 10^{12} \times 0.0695 \times 0.85 \times 1.0}=22.8  psi

The tube entrance, exit, and return losses are estimated using Equation (5.3) with α_r equal to (2n_p -1.5) from Table 5.1.

TABLE 5.1 Number of Velocity Heads Allocated for Minor Losses on Tube Side

Flow Regime Regular Tubes U-Tubes
Turbulent 2 n_{p} – 1.5 1.6 n_{p} – 1.5
Laminar, Re ≥ 500 3.25 n_{p} – 1.5 2.38 n_{p} – 1.5
\Delta P_{r}=1.334 \times 10^{-13}\left(2 n_{p}-1.5\right) G^{2} / s =1.334 \times 10^{-13}(10.5)(1,520,752)^{2} / 0.85

 

\Delta P_{ r }=3.81  psi

The sum of the two pressure drops is much greater than the allowed pressure drop. Therefore, the nozzle losses will not be calculated.
(q) Shell-side pressure drop
The friction factor is calculated using Equations (5.7) to (5.9).

f_{1}=\left(0.0076+0.000166 d_{5}\right) R e^{-0.125}=(0.0076+0.000166 \times 21.25)(20,358)^{-0.125}

 

f_{1}=0.00322  ft ^{2} / in ^{2}

 

f_{2}=\left(0.0016+5.8 \times 10^{-5} d_{5}\right) R e^{-0.157}=\left(0.0016+5.8 \times 10^{-5} \times 21.25\right)(20,358)^{-0.157}

 

f_{2}=0.000597  ft ^{2} / in ^{2}

 

f=144\left\{f_{1}-1.25\left(1-B / d_{s}\right)\left(f_{1}-f_{2}\right)\right\}

 

=144\{0.00322-1.25(1-0.3)(0.00322-0.000597)\}

f = 0.1332

The number of baffle spaces, n_{b}+1, is estimated by neglecting the thickness of the tubesheets. The baffle spacing is commonly interpreted as the center-to-center distance between baffles, which is technically the baffle pitch. In effect, the baffle thickness is accounted for in the baffle spacing. (This interpretation is inconsistent with the equation for the flow area, as, where the face-to-face baffle spacing should be used rather than the center-to-center spacing. However, the difference is usually of little practical consequence and is neglected herein.) The result is:

n_{b}+1 \cong L / B=(20 \times 12) / 6.375=37.65 \Rightarrow 38

The friction loss is given by Equation (5.6):

\Delta P_{f}=\frac{f G^{2} d_{s}\left(n_{b}+1\right)}{7.50 \times 10^{12} d_{e} s \phi}=\frac{0.1332(239,362)^{2} \times 21.25 \times 38}{7.50 \times 10^{12} \times 0.99 \times 0.785 \times 1.0}

 

\Delta P_{f}=1.06  psi

The nozzle losses will not be calculated because the initial design requires significant modification. This completes the rating of the initial design.
In summary, there are two problems with the initial configuration of the heat exchanger:
(1) The tube-side pressure drop is too large.
(2) The exchanger is over-sized.

In addition, the pressure drop on the shell-side is quite low, suggesting a poor trade-off between pressure drop and heat transfer.
To remedy these problems, both the number of tubes and the number of tube passes can be reduced. We first calculate the number of tubes required, assuming the overall heat-transfer coefficient remains constant.

A_{\text {req }}=\frac{q}{U_{D} F\left(\Delta T_{ ln }\right)_{c f}}=\frac{3,717,000}{41.9 \times 0.97 \times 191.2}=478  ft ^{2}

 

\left(n_{ t }\right)_{\text {req }}=\frac{A_{\text {req }}}{\pi D_{o} L}=\frac{478}{\pi(1.0 / 12) \times 20}=91.3 \Rightarrow 92

Taking four tube passes, the tube-count table shows that the closest count is 104 tubes in a 17.25-in. shell. The effect of these changes on the tube-side flow and pressure drop are estimated as follows.

R e \rightarrow 12,149(4 / 6)(156 / 104)=12,149

From Equation (5.19),

\Delta P_{f} \sim \frac{Ln_{p}^{2.74}}{n_{t}^{1.74}D_i^{4.74}}  (turbulent flow)          (5.19)

\Delta P_{f} \sim n_{p}^{2.74} n_{t}^{-1.74}

 

\Delta P_{f} \rightarrow 22.8(4 / 6)^{2.74}(104 / 156)^{-1.74}=15.2  psi

Since these changes leave Re (and hence G) unchanged, the minor losses are easily calculated using Equation (5.3).

\Delta P_{ r }=1.334 \times 10^{-13}(6.5)(1,520,752)^{2} / 0.85=2.36  psi

Thus, in order to meet the pressure-drop constraint, the tube length will have to be reduced significantly, to about 15 ft when allowance for nozzle losses is included. The resulting under-surfacing will have to be compensated by a corresponding increase in h_{0}, which is problematic. (Since Re_{i} remains unchanged, so does h_i.) It is left as an exercise for the reader to check the viability of this configuration.
In order to further reduce the tube-side pressure drop, we next consider an exchanger with more tubes. Referring again to the tube-count table, the next largest unit is a 19.25-in. shell containing a maximum of 130 tubes (for four passes). The tube-side
Reynolds number for this  configuration is:

R e \rightarrow 12,149(4 / 6)(156 / 130)=9719

Reducing the number of tubes to 124 (31 per pass) gives Re_{i} = 10,189. The friction loss then becomes:

\Delta P_{f} \rightarrow 22.8(4 / 6)^{2.74}(124 / 156)^{-1.74}=11.2  psi

The minor losses will also be lower, and shorter tubes can be used in this unit, further assuring that the pressure-drop constraint will be met. (The final tube length will be determined after the overall heat-transfer coefficient has been recalculated.)
Thus, for the second trial a 19.25-in. shell containing 124 tubes arranged for four passes is specified. Due to the low shell-side pressure drop, the baffle spacing is also reduced to the minimum of 0.2 d_s. (Using a baffle spacing at or near the minimum can cause excessive leakage and bypass flows on the shell-side, resulting in reduced performance of the unit [11]. The low shell-side pressure drop in the present application should mitigate this problem.)

Second Trial
Based on the foregoing analysis, we anticipate that the exchanger will have sufficient heat-transfer area to satisfy the duty. Therefore, we will calculate the overall coefficient, U_{D}., and use it to determine the tube length that is needed. The pressure drops will then be checked.
(a) Calculate h_{i}.

R e=\frac{4 \dot{m}\left(n_{p} / n_{t}\right)}{\pi D_{i} \mu}=\frac{4 \times 150,000(4 / 124)}{\pi \times 0.0695 \times 8.7}=10,189

 

h_{i}=\left(k / D_{i}\right) \times 0.023 R e^{0.8} Pr^{1 / 3}\left(\mu / \mu_{w}\right)^{0.14}

 

=(0.077 / 0.0695) \times 0.023(10,189)^{0.8}(55.36)^{1 / 3}(1.0)

 

h_{i}=156  Btu / h \cdot ft ^{2} \cdot{ }^{\circ} F

(b) Calculate h_{0}.

B=0.2 d_{s}=0.2 \times 19.25=3.85 \text { in. }

 

a_{s}=\frac{d_{5} C^{\prime} B}{144 P_{T}}=\frac{19.25 \times 0.25 \times 3.85}{144 \times 1.25}=0.103  ft ^{2}

 

G=\dot{m} / a_{5}=45,000 / 0.103=436,893  lbm / h \cdot ft ^{2}

 

R e=D_{e} G / \mu=0.0825 \times 436,893 / 0.97=37,158

 

j_{H}=0.5\left(1+B / d_{s}\right)\left(0.08 R e^{0.6821}+0.7 R e^{0.1772}\right)

 

=0.5(1+0.2)\left[0.08(37,158)^{0.6821}+0.7(37,158)^{0.1772}\right]

 

j_{H}=65.6

 

h_{o}=j_{H}\left(k / D_{e}\right) Pr^{1 / 3}\left(\mu / \mu_{w}\right)^{0.14}

 

=65.6(0.079 / 0.0825)(7.24)^{1 / 3}(1.0)

 

h_{0}=122  Btu / h \cdot ft ^{2} \cdot{ }^{\circ} F

(c) Calculate U_{D}.

U_{D}=\left[\frac{D_{o}}{h_{i} D_{i}}+\frac{D_{o} \ln \left(D_{o} / D_{i}\right)}{2 k_{\text {aibe }}}+\frac{1}{h_{o}}+R_{D}\right]^{-1}

 

=\left[\frac{1.0}{156 \times 0.834}+\frac{(1.0 / 12) \ln (1.0 / 0.839)}{2 \times 26}+\frac{1}{122}+0.0056\right]^{-1}

 

U_{D}=46  Btu / h \cdot ft ^{2} \cdot{ }^{\circ} F

(d) Calculate tube length.

q=U_{D} n_{ t } \pi D_{0} L F\left(\Delta T_{\ln }\right)_{c f}

 

L=\frac{q}{U_{D} n_{ t } \pi D_{o} F\left(\Delta T_{ ln }\right)_{q}}=\frac{3,717,000}{46 \times 124 \pi(1.0 / 12) \times 0.97 \times 191.2}=13.4  ft

Therefore, take L = 14 ft.
(e) Tube-side pressure drop.

f=0.4137 R e^{-0.2585}=0.4137(10,189)^{-0.2585}=0.03807

 

G=\frac{\dot{m}\left(n_{p} / n_{ t }\right)}{\left(\pi D_{i}^{2} / 4\right)}=\frac{150,000(4 / 124)}{\left[\pi(0.0695)^{2} / 4\right]}=1,275,469 1bm / h \cdot ft ^{2}

 

\Delta P_{f}=\frac{f n_{p} L G^{2}}{7.50 \times 10^{12} D_{i} s \phi}=\frac{0.03807 \times 4 \times 14(1,275,469)^{2}}{7.50 \times 10^{12} \times 0.0695 \times 0.85 \times 1.0}

 

\Delta P_{ r }=1.334 \times 10^{-13}\left(2 n_{p}-1.5\right) G^{2} / s=1.334 \times 10^{-13}(6.5)(1,275,469)^{2} / 0.85

 

\Delta P_{ r }=1.66  psi

Table 5.3 indicates that 4-in. nozzles are appropriate for a 19.25-in. shell. Assuming schedule 40 pipe is used for the nozzles,

TABLE 5.3 Guidelines for Sizing Nozzles

Shell Size, Inches Nominal Nozzle Diameter, Inches
4–10 2
12–17.25 3
19.25–21.25 4
23–29 6
31–37 8
39–42 10
R e_{n}=\frac{4 \dot{m}}{\pi D_{n} \mu}=\frac{4 \times 150,000}{\pi(4.026 / 12) \times 8.7}=65,432

 

G_{n}=\dot{m} /\left(\pi D_{n}^{2} / 4\right)=150,000 /\left[\pi(4.026 / 12)^{2} / 4\right]=1,696,744  lbm / h \cdot ft ^{2}

Since the flow in the nozzles is turbulent, Equation (5.4) is applicable.

\Delta P_{n}=2.0 \times 10^{-13} N_{s} G_{n}^{2} / s=2.0 \times 10^{-13} \times 1 \times(1,696,744)^{2} / 0.85

 

\Delta P_{n}=0.68  psi

The total tube-side pressure drop is:

\Delta P_{i}=\Delta P_{f}+\Delta P_{ r }+\Delta P_{n}=7.83+1.66+0.68=10.17 \cong 10.2  psi

(f) Shell-side pressure drop.
Since B/d_s = 0.2, the friction factor is given by

f=144 f_{2}=144\left(0.0016+5.8 \times 10^{-5} d_{s}\right) R e^{-0.157}

 

=144\left(0.0016+5.8 \times 10^{-5} \times 19.25\right)(37,158)^{-0.157}

f = 0.07497

n_{B}+1 \cong L / B=(14 \times 12) / 3.85=43.6 \Rightarrow 43 \text { (Rounded downward to keep } B \geq B_{\min } \text { ) }

 

\Delta P_{f}=\frac{f G^{2} d_{s}\left(n_{b}+1\right)}{7.50 \times 10^{12} d_{e} s \phi}=\frac{0.07497(436,893)^{2} \times 19.25 \times 43}{7.50 \times 10^{12} \times 0.99 \times 0.785 \times 1.0}

 

\Delta P_{f}=2.03  psi

Since the flow rate of kerosene is much less than that of the crude oil, 3-in. nozzles should be adequate for the shell. Assuming schedule 40 pipe is used,

R e_{n}=\frac{4 \dot{m}}{\pi D_{n} \mu}=\frac{4 \times 45,000}{\pi(3.068 / 12) \times 0.97}=231,034 \text { (turbulent) }

 

G_{n}=\frac{\dot{m}}{\left.\left(\pi D_{n}^{2}\right) / 4\right)}=\frac{45,000}{\left[\pi(3.068 / 12)^{2} / 4\right]}=876,545  lbm / h \cdot ft ^{2}

 

\Delta P_{n}=2.0 \times 10^{-13} N_{5} G_{n}^{2} / s=2.0 \times 10^{-13} \times 1 \times(876,545)^{2} / 0.785

 

\Delta P_{n}=0.20  psi

Note: \rho V_{n}^{2} = 1210 (lbm/ft³) (ft/s)², so impingement protection for the tube bundle will not be required to prevent erosion. The total shell-side pressure drop is

\Delta P_{o}=\Delta P_{f}+\Delta P_{n}=2.03+0.20=2.23 \cong 2.2  psi

(g) Over-surface and over-design.

U_{C}=\left[1 / U_{D}-R_{D}\right]^{-1}=[1 / 46-0.0056]^{-1}=62  Btu / h \cdot ft ^{2} \cdot{ }^{\circ} F

 

A=n_{ t } \pi D_{o} L=124 \pi \times(1.0 / 12) \times 14=454  ft ^{2}

 

U_{\text {req }}=\frac{q}{A F\left(\Delta T_{ ln }\right)_{c f}}=\frac{3,717,000}{454 \times 0.97 \times 191.2}=44  Btu / h \cdot ft ^{2} \cdot{ }^{\circ} F

 

\text { over-surface }=U_{C} / U_{\text {req }}-1=62 / 44-1=41 \%

 

\text { over-design }=U_{D} / U_{\text {req }}-1=46 / 44-1=4.5 \%

All design criteria are satisfied. The shell-side pressure drop is still quite low, but the shell-side heat-transfer coefficient (122 Btu/h . ft² . ºF) does not differ greatly from the tube-side coefficient (156 Btu/h . ft². ºF). The reader can also verify that the tube-side fluid velocity is 6.7 ft/s, which is within the recommended range. Therefore, the design is acceptable.
Final design summary
Tube-side fluid: crude oil.
Shell-side fluid: kerosene.
Shell: Type AES, 19.25-in. ID
Tube bundle: 124 tubes, 1-in. OD, 14 BWG, 14-ft long, on 1.25-in. square pitch, arranged for four passes.
Heat-transfer area: 454 ft²
Baffles: 20% cut segmental type with spacing approximately 3.85 in.
Sealing strips: one pair per ten tube rows.
Nozzles: 4-in. schedule 40 on tube side; 3-in. schedule 40 on shell side.
Materials: plain carbon steel throughout

5.11
3.14
3.17

Related Answered Questions