Holooly Plus Logo

Question 10.13: A three-phase motor is located 175 ft from its source of pow......

A three-phase motor is located 175 ft from its source of power. The conductors supplying power to the motor are 1/0 AWG aluminum. The motor has a full-load current draw of 88 A. What is the voltage drop across the conductors when the motor is operating at full load?

Step-by-Step
The 'Blue Check Mark' means that this solution was answered by an expert.
Learn more on how do we answer questions.

\mathrm{E}_{\mathrm{D}}=\frac{1.732 \times 17 ~\Omega-\mathrm{CM} / \mathrm{ft} \times 88 \mathrm{~A} \times 175}{105,500 ~\mathrm{CM}}

\mathrm{E}_{\mathrm{D}}= 4.298~ V