Holooly Plus Logo

Question 9.28: Using Kern's method, design a shell and tube heat exchanger ......

Using Kern’s method, design a shell and tube heat exchanger to cool 30 kg/s of butyl alcohol from 370 to 315 K using treated water as the coolant. The water will enter at 300 K and leave at 315 K.

Step-by-Step
The 'Blue Check Mark' means that this solution was answered by an expert.
Learn more on how do we answer questions.

Since it is corrosive, the water will be passed through the tubes.
At a mean temperature of 0.5(370 + 315) = 343 K, from Table 3, Appendix A1, the thermal capacity of butyl alcohol = 2.90 kJ/kg K and hence:
Heat load = (30 x 2.90)(370 – 315) = 4785 kW
If the heat capacity of water is 4.18 kJ/kg K, then:
Flow of cooling water = 4785/(4.18(315 – 300)) = 76.3 kg/s
The logarithmic mean temperature difference,
\theta _{m} = [(370 – 315) – (315 – 300)]/ln[(370 – 315)/(315 – 300)] = 30.7 deg K
With one shell-side pass and two tube-side passes, then from equation 9.213:

X={\frac{\theta_{2}-\theta_{1}}{T_{1}-\theta_{1}}}\quad{\mathrm{and}}\quad Y={\frac{T_{1}-T_{2}}{\theta_{2}-\theta_{1}}}            (9.213)

X = (370 – 315)/(315 – 300) = 3.67 and Y = (315 – 300)/(370 – 300) = 0.21
and from Figure 9.75:
F = 0.85 and F\theta _{m} = (0.85 x 30.7) = 26.1 deg K
From Table 9.17, an estimated value of the overall coefficient is U = 500 W/m²K and hence, the provisional area, from equation 9.212, is:

Q = UAF\theta _{m}          (9.212)
A = (4785 x 10³)/(26.1 x 500) = 367 m²

It is convenient to use 20 mm OD, 16 mm ID tubes, 4.88 m long which, allowing for the tube-sheets, would provide an effective tube length of 4.83 m. Thus:
Surface area of one tube = π(20/1000) = 0.303 m²
and: Number of tubes required = (367/0.303) = 1210
With a clean shell-side fluid, 1.25 triangular pitch may be used and, from equation 9.211:

Number of tubes, N_{t}=a(d_{b}/d_{o})^{b}               (9.211)

1210=0.249(d_{b}/20)^{2.207}

from which: d_{b} = 937 mm
Using a split-ring floating head unit, then, from Figure 9.71. the diametrical clearance between the shell and the tubes = 68 mm and:
Shell diameter, d_{s} = (937 + 68) = 1005 mm
which approximates to the nearest standard pipe size of 1016 mm.

Tube-side coefficient

The water-side coefficient may now be calculated using equation 9.218, although here, use will be made of the j_{h} factor.

Nu=(h d/k)= j_{h}R e P r^{0.33}(\mu/\mu_{s})^{-0.14}                  (9.218)

Cross-sectional area of one tube = (π/40) x 16² = 201 mm²
Number of tubes/pass = (1210/2) = 605

Thus: Tube-side flow area = (605 x 201 x 10^{-6}) = 0.122 m²
Mass velocity of the water = (76.3/0.122) = 625 kg/m²s
Thus, for a mean water density of 995 kg/m³:
Water velocity, u = (625/995) = 0.63 m/s
At a mean water temperature of 0.5(315 + 300) = 308 K, viscosity, μ = 0.8 mN s/m² and thermal conductivity, k = 0.59 W/m K.
Thus:
Re = duρ/μ = (16 x 10^{-3} x 0.63 x 995)/(0.8 x 10^{-3}) = 12540
Pr = C_{p}μ/k = (4.18 x 10³ x 0.8 x 10^{-3})/0.59 = 5.67
l/d_{i} = 4.83/(16 x 10^{-3}) = 302
Thus, from Figure 9.77, j_{h} = 3.7 x 10^{-3}, and, in equation 9.218, neglecting the viscosity term:

Nu=(h d/k)= j_{h}R e P r^{0.33}(\mu/\mu_{s})^{-0.14}                  (9.218)

(h_{i}\times16\times10^{-3})/0.59=(3.7\times10^{-3}\times12540\times5.67^{0.33})

and: h_{i} = 3030 W/m²K

Shell-side coefficient
The baffle spacing will be taken as 20 per cent of the shell diameter or (1005 x 20/100) = 201 mm
The tube pitch = (1.25 x 20) = 25 mm and, from equation 9.226:

A_{s}=d_{s}l_{B}C^{\prime}/Y              (9.226)

Cross-flow area, A_{s} = [(25 – 20)/25](1005 x 201 x 10^{-6}) = 0.040 m²
Thus: Mass velocity in the shell, G_{s} = (30/0.040) = 750 kg/m²s
From equation 9.228:

For square pitch : d_{e}=4(Y^{2}-\pi d_{o}^{2})4/\pi d_{0}=\;1.27(Y^{2}-0.785d_{o}^{2})/d_{o}(9.277)

and for triangular pitch : d_{e}=4[(0.87Y\times Y/2)-(0.5\pi d_{o}^{2}/4]/(\pi d_{o}/2)

=1.10(Y^{2}-0.917d_{o}^{2})/d_{o}          (9.228)

Equivalent diameter, d_{e} = 1.10[25² – (0.917 x 20²)]/20 = 14.2 mm
At a mean shell-side temperature of 0.5(370 + 315) = 343 K, from Appendix A1:
density of butyl alcohol, ρ = 780 kg/m³, viscosity, μ = 0.75 mN s/m², heat capacity, C_{p} = 3.1 kJ/kg K and thermal conductivity, k = 0. 16 W/m K.
Thus, from equation 9.229:

R e_{s}=G_{s}^{\prime}d_{e}/\mu=u_{s}d_{e}\rho/\mu          (9.229)

Re = G_{s}d_{e}/μ = (750 x 14.2 x 10^{-3})/(0.75 x 10^{-3}) = 14200
Pr = C_{p}μ/k = (3.1 x 10³ x 0.75 x 10^{-3})/0.16 = 14.5
Thus, with a 25 per cent segmental cut, from Figure 9.81: j_{h} = 5.0 x 10^{-3}
Neglecting the viscosity correction term in equation 9.230:

N u=(h_{s}d_{e}/k_{f})=j_{h}R e P r^{0.33}(\mu/\mu_{s})^{0.14}            (9.230)

(h_{s}\times14.2\times10^{-3})/0.16=5.0\times10^{-3}\times14200\times14.5^{0.33}

and: h_{s} = 1933 W/m²K
The mean butanol temperature = 343 K, the mean water temperature = 308 K and hence the mean wall temperature may be taken as 0.5(343 + 308) = 326 K at which \mu _{s} = 1.1 mN s/m²
Thus: (\mu/\mu_{s})^{0.14}=(0.75/1.1)^{0.14}=0.95

showing that the correction for a low viscosity fluid is negligible.

Overall coefficient
The thermal conductivity of cupro-nickel alloys = 50 W/m K and, from Table 9.16, scale resistances will be taken as 0.00020 m²K/W for the water and 0.00018 m²K/W for the organic.

Based on the outside area, the overall coefficient is given by:

1/U=1/h_{o}+R_{o}+x_{w}/k_{w}+R_{i}/(d_{o}/d_{i})+(1/h_{i})(d_{o}/d_{i})

= (1/1933) + 0.00020 + [0.5(20 – 16) x 10^{-3}/50] + (0.00015 x 20)/16 + 20/(3030 x 16)
= 0.00052 + 0.00020 + 0.00004 + 0.000225 + 0.00041 = 0.00140 m²K/W

and: U = 717 W/m²K
which is well in excess of the assumed value of 500 W/m²K.

Pressure drop

On the tube-side, Re = 12450 and from Figure 9.78, j_{f} = 4.5 x 10^{-3}
Neglecting the viscosity correction term, equation 9.225 becomes:

-\Delta P_{total}=N_{P}[4j_{f}(l/d_{i})(\mu/\mu_{s})^{m}+1.25](\rho u^{2})                   (9.225)

ΔP_{t} = 2(4 x 4.5 x 10^{-3}(4830/16) + 1.25)(995 x 0.63²) = 5279 N/m² or 5.28 kN/m²
which is low, permitting a possible increase in the number of tube passes. On the shell-side, the linear velocity, (G_{s}/ρ) = (750/780) = 0.96 m/s
From Figure 9.82, when Re = 14200, j _{f} = 4.6 x 10^{-2}
Neglecting the viscosity correction term, in equation 9.231:

-\Delta P_{s}=4j_{f}(d_{s}/d_{e})(l/l_{B})(\rho u_{s}^{2})(\mu/\mu_{s})^{-0.14}                  (9.231)

– ΔP_{s} = (4 x 4.6 x 10^{-2})(1005/14.2)(4830/201)(780 x 0.96²)
= 224950 N/m² or 225 kN/m²
This value is very high and thought should be given to increasing the baffle spacing. If this is doubled, this will reduce the pressure drop by approximately (1/2)² = 1/4 and:

– ΔP_{s} = (225/4) = 56.2 kN/m² which is acceptable.

Since h_{o}\propto R e^{0.8}\propto u^{0.8}

h_{o}=1933(1/2)^{0.8}=1110\ \mathrm{W/m^{2}K}

which gives an overall coefficient of \underline{\underline{561\ W/m^{2}K}} which is still in excess of the assumed value of 500 W/m²K.

Table 9.16. Thermal resistances of scale deposits from various fluids
m²K/kW ft²h°F/Btu m²K/kW ft²h°F/Btu
Water* Steam
distilled 0.09 0.0005 good quality, oilfree 0.052 0.0003
sea 0.09 0.0005
clear river 0.21 0.0012 poor quality, oilfree 0.09 0.0005
untreated cooling tower 0.58 0.0033
treated cooling tower 0.26 0.0015 exhaust from reciprocating engines 0.18 0.001
treated boiler feed 0.26 0.0015
hard well 0.58 0.0033 Liquids
treated brine 0.27 0.0015
Gases organics 0.18 0.001
air 0.25-0.50 0.0015-0.003 fuel oils 1.0 0.006
solvent vapours 0.14 0.0008 tars 2.0 0.01

*For a velocity of 1 m/s (≈ 3 ft/s) and temperatures of less than 320 K (122°F)

Table 9.17. Approximate overall heat transfer coefficients U for shell and tube equipment
Overall U
Hot side Cold side W/m²K Btu/h ft² °F
Condensers
Steam (pressure) Water 2000-4000 350-750
Steam (vacuum) Water 1700-3400 300-600
Saturated organic solvents (atmospheric) Water 600-1200 100-200
Saturated organic solvents (vacuum some non-condensable) Water -brine 300-700 50-120
Organic solvents (atmospheric and high non-condensable) Water -brine 100-500 20-80
Organic solvents (vacuum and high non-condensable) Water -brine 60-300 10-50
Low boiling hydrocarbons (atmospheric) Water 400-1200 80-200
High boiling hydrocarbons (vacuum) Water 60-200 10-30
Heaters
Steam Water 1500-4000 250-750
Steam Light oils 300-900 50-150
Steam Heavy oils 60-400 10-80
Steam Organic solvents 600-1200 100-200
Steam Gases 30-300 5-50
Dowtherm Gases 20-200 4-40
Dowtherm Heavy oils 50-400 8-60
Evaporators
Steam Water 2000-4000 350-750
Steam Organic solvents 600-1200 100-200
Steam Light oils 400-1000 80-180
Steam Heavy oils (vacuum) 150-400 25-75
Water Refrigerants 400-900 75-150
Organic solvents Refrigerants 200-600 30-100
Heat exchangers (no change of state)
Water Water 900-1700 150-300
Organic solvents Water 300-900 50-150
Gases Water 20-300 3-50
Light oils Water 400-900 60-160
Heavy oils Water 60-300 10-50
Organic solvents Light oils 100-400 20-70
Water Brine 600-1200 100-200
Organic solvents Brine 200-500 30-90
Gases Brine 20-300 3-50
Organic solvents Organic solvents 100-400 20-60
Heavy oils Heavy oils 50-300 8-50
9.75
9.71
9.77
9.81
9.78
9.82

Related Answered Questions

Question: 9.32

Verified Answer:

Assuming that the height of the fin is small compa...