A 13.8-kV, 50-MVA, 0.9-power-factor-lagging, 60-Hz, four-pole Y-connected synchronous generator has a direct-axis reactance of 2.5 Ω, a quadrature-axis reactance of 1.8 Ω, and an armature resistance of 0.2 Ω. Friction, windage, and stray losses may be assumed negligible. The generator’s open-circuit characteristic is given by Figure P5-1.
Figure P4-1
(a) How much field current is required to make the terminal voltage V_T (or line voltage V_T ) equal to 13.8 kV when the generator is running at no load?
(b) What is the internal generated voltage of this machine when it is operating at rated conditions? How does this value of \mathbf{E}_A compare to that of Problem 4-2b?
(c) What fraction of this generator’s full-load power is due to the reluctance torque of the rotor?