Selecting a Fast-Acting Fuse for Protecting a Thyristor
A fuse is connected in series with each thyristor of type S30EF in the single-phase full converter, as shown in Figure 10.1a. The input voltage is 240 V, 60 Hz, and the average current of each thyristor is I_a = 400 A. The ratings of thyristors are I_{T(AV)} = 540 A, I_{T(RMS)} = 850 A, I^2t = 300 kA^2s at 8.33 ms, i^2\sqrt{t} = 4650 kA^2\sqrt{s} , and I_{TSM} = 10 kA with reapplied V_{RRM} = 0 , which may be the case if the fuse opens within a half-cycle. A 540-A fuse has the ratings of a maximum current I_{max} = 8500 A, a fuse i^2t = 280 KA^2, and the total clearing time t_c = 8 ms. The resistance of fault circuit is negligible and inductance is L = 0.07 mH. Determine the suitability of the fuse to protect the devices.