Question 10.8: Use Xist to rate the initial configuration for the vertical ...

Use Xist to rate the initial configuration for the vertical thermosyphon reboiler of Example 10.4 and compare the results with those obtained previously by hand.

The blue check mark means that this solution has been answered and checked by an expert. This guarantees that the final answer is accurate.
Learn more on how we answer questions.

Data from Example 10.4 are entered on the Xist input forms as indicated below. Parameters not listed are either left at their default settings or left unspecified to be calculated by the program.
(a) Input Summary

Case mode: Rating Service type: Thermosiphon reboiler
Hot fluid: Shell side

(b) Geometry/Exchanger

TEMA type: AEL Shell Orientation: Vertical
Shell ID: 15.25 in.

(c) Geometry/Tubes.

Tube OD: 1 in. Tube passes: 1
Average wall thickness: 0.083 in. Tube length: 8 ft
Tube pitch: 1.25 in. Tube count: 106
Tube layout angle: 30°

(d) Geometry/Baffles.

Baffle cut: 35% Central baffle spacing: 6.1 in.

(e) Geometry/Tube Layout/Bundle Clearances.
Pairs of sealing strips: None
(f) Geometry/Nozzles.

Shell side Tube side
Inlet ID: 4.026 in. Inlet ID: 6.065 in.
Number: 1 Number: 1
Outlet ID: 2.067 in. Outlet ID: 10.02 in.
Number: 1 Number: 1

(g) Geometry/Thermosyphon Reboiler.
Reboiler pressure location: At column bottom liquid surface
(h) Geometry/Thermosiphon Reboiler/Piping.
The detailed piping forms are used here to illustrate the procedure. They are invoked by checking the box for detailed piping on the main piping panel. The inlet piping panel is shown below:

The piping elements are selected from a list box that appears when a blank field in the first column is clicked. In this case there are only three elements because the straight pipe equivalent length is assumed to account for all entrance, exit, and fitting losses. Height changes are negative in the downward direction and positive in the upward direction. Height changes of individual elements are arbitrary here as long as they total to negative 8 ft. This puts the lower tubesheet a vertical distance of 8 ft below the liquid surface in the column sump. The outlet piping form is similar and is shown below.

The outlet header extends from the upper tubesheet to the return pipe. Since the upper tubesheet is at the same elevation as the liquid surface in the column sump, the specified height change puts the return pipe a vertical distance of 2 ft above the surface of the liquid in the sump. The value assumed for this distance has a relatively small effect on the calculations. In practice, however, the bottom of the return line should be at least 6 in. above the highest liquid level expected in the column sump.
(i) Control/Methods/Condensation.
Pure component: Yes
(j) Process

Hot fluid  Cold fluid
Fluid name Steam Cyclohexane
Phase Condensing Boiling
Flow rate (1000 lb/h) 2.397 113.814
Inlet fraction vapor 1 0
Outlet fraction vapor 0
Operating pressure (psia) 18 16
Fouling resistance (h · ft²·ºF/Btu) 0 0.0005

(k) Hot fluid properties.
VMGThermo and Steam95 are selected for the property package. On the conditions panel, property sets is selected as the temperature point method. Pressure levels of 20, 18, and 16 psia are specified with a temperature range of 200º F to 230º F, and the number of data points is set at 20.
(l) Cold fluid properties.
VMGThermo and the Advanced Peng–Robinson method are selected for the cyclohexane stream. Selecting property sets for the temperature point method, pressure levels of 20, 18, and 16 psia are specified, with a temperature range of 180º F to 220º F. The number of data points is again set at 20.
The Xist Output Summary for this case is shown below, from which the unit is seen to be under-designed by about 20%, in agreement with the hand calculation. Data from the Output Summary and detailed output files were used to prepare the results comparison shown in the table below. The heat-transfer coefficients and pressure drops calculated by Xist agree fairly well with the hand calculations despite the fact that the circulation rates computed by the two methods differ by a large amount.

Item Hand Xist
Circulation rate (lb/h) 113,814 70,919
h_{i} (Btu/h· ft²·ºF) 565^{a} 513
h_{o} (Btu/h · ft²·ºF) 1500 (assumed) 1379
U_{D} (Btu/h· ft²·ºF) 243^{a} 257
Δ P_{i} (psi)^{c} 0.862 0.863
Δ P_{o} (psi) 0.56
Δ T_{m}  (ºF) 34.7^{b} 33.4
\left(\hat{q} / \hat{q}_c\right)_{\max } 0.48 0.29
Under-design (%) 20 19.8

^{a} Area-weighted average of values for sensible heating and boiling zones.
^{b} Value for boiling zone.
^{c} Friction and acceleration only; excluding entrance, exit, and static head losses.

The tube-side pressure drop was not explicitly calculated in Example 10.4, although all parameters needed for the calculation were evaluated. For completeness, the friction and acceleration losses are computed here.

\Delta P_{a c c}=\frac{G_t^2 \gamma}{3.75  \times  10^{12} s_L}=\frac{(283,029)^2  \times  10.77}{3.75  \times  10^{12}  \times  0.7208}=0.3192  psi

For the sensible heating zone, the friction loss is:

\Delta P_{f, B C}=\frac{f_t L_{B C} G_t^2}{7.50  \times  10^{12} D_t s_L}=\frac{0.0319  \times  2.9(283,029)^2}{7.50  \times  10^{12}  \times  0.0695  \times  0.7208}=0.0197  psi

For the boiling zone, the friction loss is:

\Delta P_{f, C D}=\frac{f_t L_{C D} G_t^2 \bar{\phi}_{L O}^2}{7.50  \times  10^{12} D_t s_L}=\frac{0.0319  \times  5.1(283,029)^2  \times  15.08}{7.50  \times  10^{12}  \times  0.0695  \times  0.7208}=0.5231  psi

The total friction loss is:

\Delta P_f=\Delta P_{f, B C}+\Delta P_{f, C D}=0.0197+0.5231=0.5428  psi

Therefore,

\Delta P_{a c c}+\Delta P_f=0.3192+0.5428=0.862  psi

Xist Output Summary for Example 10.8

10...8
10.8
10..8

Related Answered Questions

Question: 10.2

Verified Answer:

(a) Make initial specifications. (i) Fluid placeme...
Question: 10.9

Verified Answer:

Starting from the 15.25-in. unit rated in the prev...