A strainer has a C_{ν} rating of 60. It is to be used in a system to filter 50 gpm of water. What head loss can be expected?
Equation 10-30 will yield the desired result:
l_{f} = 2.31 \left(\frac{\dot{Q}}{C_{ν}}\right)^{2} (10-30)
l_{f} = 2.31 \left(\frac{50}{60}\right)^{2} = 1.6 ft of water
Heating and cooling units and terminal devices usually have head loss information furnished by the manufacturer. The head loss is often used to indicate the flow rate for adjustment of the system. Equation 10-29 may be used to estimate head loss at other than specified conditions.
\frac{l_{f1}}{l_{f2}} = \left(\frac{\dot{Q}_{1}}{\dot{Q}_{2}}\right)^{2} (10-29)