Holooly Plus Logo

Question 10.11: What pressure drop should be used for the steam piping of a ......

What pressure drop should be used for the steam piping of a system if the length of the longest run, including fittings, is 400 ft with an allowance of 400 ft for fittings? Initial pressure must not exceed 5 psig.

Step-by-Step
The 'Blue Check Mark' means that this solution was answered by an expert.
Learn more on how do we answer questions.

The total equivalent length of the longest run is 800 ft. From Table 10-4a the total allowable pressure drop is given as 1.5 psi, at a system pressure of 5 psig. The pressure drop per unit length of 100 ft is

∆P/L = 1.51(100/800) = 0.19 ≈ 0.2 psi/100 ft

This value is in fair agreement with the suggested value in Table 10-4a. The steam piping may then be sized using ∆P/L = 0.2 psi/100 ft, the capacity of the pipe section in lbv/hr, and the velocity criterion cited previously.

Table 10-4a Pressure Drops Used for Sizing Steam Pipe^{a}

Initial Steam

Pressure, psig

 Pressure Drop

per 100 ft

Total Pressure Drop in

Steam Supply Piping

0 0.5 oz/in.² 1 oz/in.²
1 2 oz/in.² 1 to 4 oz/in.²
2 2 oz/in.² 8 oz/in.²
5 4 oz/in.² 1.5 psi
10 8 oz/in.² 3 psi
15 1 psi 4 psi

Equipment, control valves, and so forth must be selected
based on delivered pressures.
Source: Reprinted by permission from ASHRAE Handbook,
Fundamentals Volume, 1997.

Related Answered Questions

Question: 10.7

Verified Answer:

Equation 10-30 will yield the desired result: [lat...