Question 10.4: Consider an open office space with 150 m2 located in Denver,......

Consider an open office space with 150 m2 located in Denver, CO, with a total window area of 20 m², with double-pane glazing, which has a visible transmittance of 0.55. The office space has 10 fluorescent fixtures, each rated at 52 \ W. Determine the energy use and cost savings due to daylighting harvesting strategies. Assume that without daylighting harvesting, each fixture is operated 8 \ h/day when daylighting can be harvested, 5 \ days/week, 250 \ weeks/year. The cost of electricity is 0.10/kWh.

TABLE 10.5
Coefficients a and b of Equation 10.4 for Various Locations throughout the World

b a Location b a Location
72.7 19.2 Casper 74.3 19.6 Atlanta
70.9 17.8 Portland 71.7 18.4 Chicago
69.8 18.8 Montreal 72.9 19.4 Denver
70.6 19.1 Quebec 74.8 22.3 Phoenix
68.7 16.9 Vancouver 67.0 18.7 New York City
70.5 20.0 Regina 70.8 18.7 Washington, DC
70.5 19.3 Toronto 67.1 18.7 Boston
70.9 19.6 Winnipeg 74.8 25.1 Miami
67.3 19.4 Shanghai 74.0 20.6 San Francisco
72.4 20.2 K-Lumpur 69.2 16.6 Seattle
73.7 23.3 Singapore 74.2 22 Los Angeles
74.2 27.0 Cairo 70.0 18.8 Madison
74.7 36.9 Alexandria 74.7 21.6 Houston
74.1 25.2 Tunis 72.9 19.7 Fort Worth
71.2 29.4 Sao Paulo 70.7 17.9 Bangor
73.6 28.6 Mexico 72.6 18.8 Dodge City
67.7 20 Melbourne 70.4 20 Nashville
72.4 16.0 Roma 74.4 20.2 Oklahoma City
69.7 15.2 Frankfurt 72.3 18.6 Columbus
65.3 22.0 Kuwait 71.5 17.9 Bismarck
72.7 21.2 Riyadh 72.0 18.2 Minneapolis
72.30 18.9 Omaha
Step-by-Step
The 'Blue Check Mark' means that this solution was answered by an expert.
Learn more on how do we answer questions.

Based on Equation 10.4, using the coefficients a = 19.4 and b = 72.9, the percent reduction in electrical lighting associated with daylighting harvesting is

f_d=b\left[1-\exp \left\lgroup\frac{-a\tau _wA_w}{A_f} \right\rgroup \right]                                      (10.4)

f_d=72.9*\left[1-\exp \left\lgroup-19.4*0.55*\frac{20}{150} \right\rgroup \right]=55.3\%

Therefore, the savings in annual electrical energy use for the office space are computed as follows:

\Delta kWh=55.3\%*10*52*\frac{1}{1000}*8*250=2876 \ kWh/year

Thus, the annual energy use cost saving is $287.6/year that can justify the installation of one or two photosensors for implementing daylighting control in the open office space since one sensor costs about $250.