Holooly Plus Logo

Question 8.7: Determine all the required sections of a unit substation for......

Determine all the required sections of a unit substation for a radial distribution system shown in Figure 8.21. Then, size the electrical room assuming the unit substation is placed in the center of the room.

تعليق توضيحي 2023-02-21 201529
Step-by-Step
The 'Blue Check Mark' means that this solution was answered by an expert.
Learn more on how do we answer questions.

Using the different steps outlined in the general design procedure, the unit substation sections can be selected for the system of Figure 8.21.

1. Primary section:

I_L=\frac{1750 \ kVA}{(1.732)(13.8 \ kV)}=73.2 \ A

→ Use 600 \ A,  15 \ kV, W=36 \ in., H=90 \ in., D=54 \ in. primary section

2. Transformer section:
Table 8.6 → W = 100 \ in., H = 100 \ in., D = 54 \ in.

3. Main secondary section:

I_L=\frac{1750 \ kVA}{\sqrt{3} (0.48 \ kV)}=2105 \ A \\I_{CB}=1.25\times I_L=2631 \ A

Table 8.7 → use 3000 \ A  CB (I_{SC}=65,000 \ A <50,000 \ A)
Table 8.8 → unit \#1,W=30 \ in.

4. Feeder section:

I_L=700 \ A ,I_{CB}=840 \ A

Table 8.7 → 1600 \ A  CB (I_{SC}=50,000 \ A <40,000 \ A)
Table 8.8 → use unit \#3,W=26 \ in.
Each can handle three panels → two feeder sections are needed

5. Electrical room size: Figure 8.22 shows the layout of the unit substation based on the selection of all the sections. Since the total width of the unit substation is 218 \ in. or 18.16 \ ft and its depth is 54 \ in., the size of the room with a clearance distance of 6 \ ft in all sides can be determined:

Electrical room size  = 30.16 \ ft(width)\times 16.5 \ ft(depth)

TABLE 8.6
Ratings and Dimensions of Dry-Type Transformer Sections Suitable for Unit Substations
kVA Rating of the Transformer Dimensions of the Transformer Section^a
5 kV Systems 15 kV Systems
H W D H W D
111.5 90 30 54 90 30 54
150 90 30 54 90 30 54
225 90 30 54 90 42 54
300 90 42 54 90 90 54
500 90 42 54 90 90 54
750 90 90 54 90 90 54
1000 90 90 54 90 100 54
1500 90 100 54 90 100 54
2000 90 100 54 100 100 54
2500 90 100 54 100 100 54
^a The dimensions are expressed in inches and should be multiplied by 2.54 to
express them in cm.
TABLE 8.7
Frame Sizes and Typical Ratings for Low-Voltage Power Circuit Breakers
Frame Size (A) Trip Ratings^a (A) Instantaneous Trip
Interrupting Symmetrical
Current Ratings (A)
Short-Time (0.5 s Delay)
Trip Interrupting
Symmetrical Ratings (A)
208/240 V 480 V 600 V 240 V 480 V 600 V
600 50–600 42,000 30,000 30,000 30,000 30,000 30,000
600 50–800 42,000 30,000 30,000 30,000 30,000 30,000
1600 50–1600 65,000 50,000 42,000 50,000 50,000 42,000
2000 50–2000 65,000 50,000 50,000 50,000 50,000 50,000
3000 1200–3000 85,000 65,000 65,000 65,000 65,000 65,000
4000 1600–400 130,000 85,000 85,000 85,000 85,000 85,000
^a Standard trip ratings include 50, 100, 150, 200, 225, 300, 400, 600, 800, 1200, 2000, 2400, 3000, and 4000 A.
TABLE 8.8
Ratings and Dimensions of Main Feeder and Subfeeder Sections
Unit No. Width [in. (cm)] Maximum Current
Ratings (A)
Number of
Compartments
Applications
Unit 1 30 (76) 3000 1 Main secondary sections
Unit 2 18 (46) 600 4 Feeder sections
Unit 3 26 (66) 1600 3 Feeder sections
Unit 4 30 (76) 3000 3 Feeder sections
Unit 5 34 (86) 4000 2 Main secondary or feeder sections
Unit 6 26 (66) 600–1600 4 Feeder sections (with different
feeder ratings)
تعليق توضيحي 2023-02-21 201352

Related Answered Questions