Holooly Plus Logo

Question 14.7: Predicting Part-Load Behavior Using the Degradation Factor W......

Predicting Part-Load Behavior Using the Degradation Factor

We will use the results of Example 14.4 to illustrate the use of the degradation factor approach to predicting part-load performance of a unitary chiller. The same chiller is operated under part load where the cooling load to be met is only 350 kW. What will be the corresponding electric draw of the compressor? The manufacturer has not  specified a value for the degradation factor.
Given: \dot{Q}_{cool} = 350  kW, and from Example 14.4\dot{W}_{comp,ss} = 111.55  kW and \dot{Q}_{cool,ss} = 500  kW.
Assume: C_{d} = 0.25
Find: \dot{W}_{comp} and COP

Step-by-Step
The 'Blue Check Mark' means that this solution was answered by an expert.
Learn more on how do we answer questions.

From Equation 14.27: PLR = (350/500) = 0.7

PLR = min \{ 1, \frac{\dot{Q}_{cool}}{\dot{Q}_{cool,ss}} \}        (14.27)
From Equation 14.30: PLF = 1−0.25 × (1−0.7) = 0.925

PLF = 1  –  C_{d} \times (1  –  PLR)           (14.30)
Finally, from Equation 14.29:

\dot{W}_{comp} = \dot{W}_{comp,ss} \times \left\lgroup \frac{PLR}{PLF} \right\rgroup                   (14.29)
\dot{W}_{comp} = 111.55 \times \left\lgroup \frac{0.7}{0.925} \right\rgroup = 84.42  kW
which results in a part-load COP = (350/84.42) = 4.15
The steady-state COP_{ss} = (500/111.55) = 4.48; thus, cycling has reduced the COP by 7.4%

Related Answered Questions