A process model for a liquid storage system is given by Chien and Fruehauf (1990):
\tilde{G}(s)=\frac{Ke^{-7.4s}}{s}
Use Table below to calculate PI and PID controller settings for K = 0.2 and \tau_{c} = 8. Repeat for \tau_{c} = 15 and do the following:
(a) Compare the four controllers for unit step changes in the set point and disturbance, assuming that G_{d} = \tilde{G}.
(b) In order to characterize the robustness of each controller of part (a), determine K_{\max}, the largest value of K that results in a stable closed-loop system for each controller.