Use the DS design method to calculate PID controller settings for the process:
G = \frac{2e^{-s}}{(10s+1)(5s+1)}
Consider three values of the desired closed-loop time constant: τ_{c}=1,3, and 10. Evaluate the controllers for unit step changes in both the set point and the disturbance, assuming that G_{d} = G .
Repeat the evaluation for two cases:
(a) The process model is perfect (\widetilde{G} = G).
(b) The model gain is incorrect, \widetilde{K} = 0.9, instead of the actual value, K=2.
Thus,
\widetilde{G} = \frac{0.9e^{-s}}{(10s+1)(5s+1)}